IM 1E10C1-E
5-1
5. FUNCTION AND DATA SETTINGS
5.
FUNCTION AND DATA SETTINGS
A Magnetic flowmeter calculates volume flow rate from a minute voltage that corre-
sponds to the flow velocity of a fluid an outputs as a 4 to 20mA signal.
The three parameters must be set to obtain a correct signal.
Nominal size, flow span and meter factor must be set.
This chapter explaines how to set flow span, other functions and data settings.
Please set data correctly.
Basic Key Operations
Key Operation
Item
SET
SHIFT
SET
SHIFT
INC
SET (Twice)
How to change the display into the setting mode?
How to move the cursor on the display during parameter setting?
How to change the display into the data changing mode?
How to move the cursor in the data changing mode?
How to change the data?
Finally, How to input the set data?
•
you cannot set the leftmost digit of display to numeric value
greater than "4". If the leftmost digit of the span must be "4" or
more, set the numeric value beginning from the digit second
from the left on the display (the fourth digit).
•
If the leftmost digit of the display is set to "3", the digits to its
right can be set to "0" only, regardless of the decimal point
position.
NOTE
NOTE