IM 1E10C1-E
6-10
6. OPERATION VIA BRAIN TERMINAL
6.5.3
Setting Meter Factor
The meter factor is engraved on the data plate of the combined flow tube.
Example: set “1.1200” as meter factor.
Select “B08:MF” by feeding the page with the arrow key and press
ENTER key to call up the following data setup panel.
Display
Description
Turn the power on and the panel as shown on the left appears after
“Please wait...” is displayed for a few seconds.
Pressing the ENTER key causes the initial data panel to be displayed.
Pressing the F4 key or ENTER key causes the menu panel to be
displayed.
Use the arrow key to select “B:SET” with the arrow key and press
the ENTER key.
Then, the parameter panel is displayed.
--WELCOME--
BRAIN TERMINAL
ID:BT200
CHECK CABLE CONNECTION
AND PRESS THE ENT KEY.
UTIL
FEED
ENTER
PARAM
B01:TAG NO
B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s
DATA
DIAG
ESC
PARAM
01:MODEL
SE14-A00
02:TAG NO.
03:SELF CHECK
GOOD
OK
MENU
A:DISPLAY
B:SET
C:ADJUST
D:DISP SEL
E:TOTAL SET
F:PULSE SET
ENTER
ENTER
HOME
SET
ADJ
ESC
F4
or
ON/OFF
ENTER
PARAM
B06:SIZE UNIT
inch
B07:NOMINAL SIZE
2.00 inch
B08:MF
1.0000
ESC
Press ENTER key on the parameter panel to display the data setup
panel as shown on the left.
(If the security panel appears, enter the security code.*)
Select “1.1200” using the alphanumeric keys. Default:1.0000
SET
B08:MF
1.0000
0
ESC
DATA
DIAG
“1.1200”
CLR
DEL
* For entry of the security code, see IM1C0A11-01E.