8. ACTUAL OPERATON
8.2 Self-diagnostics Functions
The self-diagnostics function displays instrument internal errors, input/output signal
abnormalities, setting errors, and other problems.
When an alarm occurs, the alarm number that the error has occurred and normal data
are alternately indicated on the indicator of ADMAG SE.
However, alarms are only displayed during flow rate data display mode and when
parameter numbers are being changed in the setting mode. (Alarms are not displayed
when data items are being changed.)
The current output during the alarm occurrence can be selected from among the
followings. See “8.2.1 Output Status during Alarm Occurence.”
• 2.4mA or less
• 4mA
• HOLD
• 21.6mA or more
When the BT200 is used, alarms are displayed in “A60 to N60:SELF CHECK”
parameter.
When the HART Communicator is used, alarms are displayed in “Status group 1 to
3” parameters. There are two methods for self-diagnostics, every transmission and
manually executing the “Self test” command. See “8.2.2 Self-diagnostics Using
HART Communicator.”
When an error message appears, follow “8.2.3 Error Description and Countermea-
sure.”.
8.2.1
Output Status during Alarm Occurrence
---
GOOD
Self test OK
ON
Normal
Normal
---
ERROR
Error
OFF
Fixed*
Stop
Err-02
uP FAULT
uP fault
OFF
21.6mA or more**
Stop
Err-03
EEPROM FAULT
EEPROM fault
OFF
21.6mA or more**
Stop
Err-05
A/D FAULT
A/D fault
OFF
Fixed*
Stop
Err-06
SIGNAL OVERFLOW
Signal overflow
OFF
Fixed*
Stop
Err-07
COIL OPEN
Coil open
OFF
Fixed*
Stop
Err-08
SPAN VEL.>10m/s
Vel. span>10m/s
OFF
Fixed*
Stop
Err-09
SPAN VEL.<0.3m/s
Vel. span<0.3m/s
OFF
Fixed*
Stop
Err-10
P.SPAN>1000p/s
P.span>1000p/s
OFF
Fixed*
Stop
Err-11
P.SPAN>500p/s
P.span>500p/s
OFF
Fixed*
Stop
Err-12
P.SPAN>25p/s
P.span>25p/s
OFF
Fixed*
Stop
Err-13
P.SPAN>15p/s
P.span>15p/s
OFF
Fixed*
Stop
Err-14
P.SPAN>10p/s
P.span>10p/s
OFF
Fixed*
Stop
Err-15
P.SPAN>5p/s
P.span>5p/s
OFF
Fixed*
Stop
Err-16
P.SPAN<.0001p/s
P.span<.0001p/s
OFF
Fixed*
Stop
Err-17
T.SPAN>1000p/s
T.span>1000p/s
OFF
Fixed*
Stop
Err-18
T.SPAN>.0001p/s
T.span<.0001p/s
OFF
Fixed*
Stop
Err-19
4-20 LMT ERROR
Analog lmt error
OFF
Fixed*
Stop
Err-20
EMPTY PIPE
Empty pipe
OFF
Fixed*
Stop
Err-21
MULTIRANGE ERROR
Multi range err
OFF
Fixed*
Stop
Err-22
COIL SHORT
Excitation failure
OFF
Fixed*
Stop
Err-23
EEPROM NO SET
EEPROM no set
OFF
21.6mA or more**
Stop
Err-24
EEPROM DEFAULT
EEPROM default
OFF
Fixed*
Stop
Err-25
—
Dev id not entered
OFF
Fixed*
Stop
Display detail
BRAIN Terminal
HART
Communicator
Indicator
of SE
Alarm
Contact
Output
Current Output
Total/Pulse
Output
Note) *Depending on the setting in “4-20 ALM OUT (Analog alarm out)”.
**When optional code /C1 is selected, current output becomes 2.4mA or less.