![YASKAWA Z1000U Series Programming Manual Download Page 244](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538244.webp)
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S6-07
(323C)
Output Phase Loss
Detection Level for
Dynamic Audible Noise
Control
Outp Ph Loss Lv1
Sets the output phase loss detection level for Dynamic Audible
Noise Control. Decrease the setting in steps of 10% when output
phase loss is detected erroneously. This setting rarely needs to be
changed.
Default:
100.0%
Min.: 10.0
Max.: 100.0
A.13 S: Special Application
244
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual