Setting 0: Auto detection
Setting 1: 10 kbps
Setting 2: 20 kbps
Setting 3: 50 kbps
Setting 4: 125 kbps
Setting 5: 250 kbps
Setting 6: 500 kbps
Setting 7: 800 kbps
Setting 8: 1 Mbps
u
BACnet Parameters
Parameters F6-45 to F6-49 set the drive to operate on a BACnet network.
n
F6-45: BACnet Node Address
Sets the node address for a BACnet option card.
No.
Parameter Name
Setting Range
Default
F6-45
BACnet Node Address
0 to 127
1
n
F6-46: BACnet Baud Rate
Sets the node address for a BACnet option card.
No.
Parameter Name
Setting Range
Default
F6-46
BACnet Baud Rate
0 to 8
3
Setting 0: 1200
Setting 1: 2400
Setting 2: 4800
Setting 3: 9600
Setting 4: 19200
Setting 5: 38400
Setting 6: 57600
Setting 7: 76800
Setting 8: 115200
n
F6-47: Rx to Tx Wait Time
Sets the wait time between receiving and sending for BACnet.
No.
Parameter Name
Setting Range
Default
F6-47
Rx to Tx Wait Time
5 to 65 ms
5 ms
n
F6-48: BACnet Device Object Identifier 0
Sets the least significant word for BACnet.
No.
Parameter Name
Setting Range
Default
F6-48
BACnet Device Object Identifier 0
0 to FFFF
0
n
F6-49: BACnet Device Object Identifier 1
Sets the least significant word for BACnet.
No.
Parameter Name
Setting Range
Default
F6-49
BACnet Device Object Identifier 1
0 to 3F
0
u
DeviceNet Parameters
Parameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.
1.6 F: Option Settings
74
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual