Register No.
Contents
00E2H
oFC1
o
Contents (CN5-C)
bit 0
Option RAM Fault (oFC10)
bit 1
Option Operation Mode Fault (SLMOD) (oFC11)
bit 2
Unit Receive CRC Error (oFC12)
bit 3
Unit Receive Frame Error (oFC13)
bit 4
Unit Receive Abort Error (oFC14)
bit 5
Option Receive CRC Error (oFC15)
bit 6
Option Receive Frame Error (oFC16)
bit 7
Option Receive Abort Error (oFC17)
bit 8 to F
Reserved
00E3H
Reserved
00E4H
oFC5
o
Contents (CN5-C)
bit 0
Encoder Option AD Conversion Error (oFC50)
bit 1
Encoder Option Analog Circuit Error (oFC51 )
bit 2
Encoder Communication Timeout (oFC52 )
bit 3
Encoder Communication Data Error (oFC53)
bit 4
Encoder Error (oFC54)
bit 5
Resolver Error (oFC55)
bit 6 to F
Reserved
00E5H to 00E9H
Reserved
00EAH
Fault contents 11
bit 0 to 6
Reserved
bit 7
Damping Resistor Overheat (doH)
bit 8
Snubber Discharge Resistor Overheat (SoH)
bit 9
Internal Resistance Fault (Srr)
bit A to D
Reserved
bit E
Safety Circuit Fault (SCF)
bit F
Reserved
00EBH to 00FAH
Reserved
00FBH
Output Current
<2>
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> Display is in the following units:
2
o
0028, 2
o
0042, and 4
o
0011 to 4
o
0027: 0.01 A units
2
o
0054 to 2
o
0248 and 4
o
0034 to 4
o
0414: 0.1 A units
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04 or E5-04 depending on the motor being used.
B.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
307