![YASKAWA Z1000U Series Programming Manual Download Page 190](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538190.webp)
Figure 2.43 Disconnected Removable Terminal Board
4.
Disconnect all option cards and options, making sure they are intact before reusing.
5.
Replace the drive and wire the main circuit.
n
Installing the Drive
1.
After wiring the main circuit, connect the terminal block to the drive as shown in
. Use the installation screw
(M3: 0.49 - 0.73 N·m) to fasten the terminal block into place.
Figure 2.44 Install the Terminal Board
2.
Reconnect options for the new drive the same way the options were connected in the old drive. Connect option boards
to the same option ports in the new drive that were used in the old drive.
3.
Replace the terminal cover.
4.
After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If an
oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting parameter
A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through o4-12 to 0, and
parameter o4-13 to 1.
Note:
1.
When replacing a previous generation product with U1000, do not use the previous generation terminal board.
2.
Set the correct value in o2-04.
Refer to Defaults by Drive Model on page 259
for details.
3.
Contact Yaskawa or a Yaskawa representative for instructions on replacing the terminal board. Improperly replacing the terminal board
will result in drive malfunction.
2.6 Drive Replacement
190
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual