Inspection Area
Inspection Points
Corrective Action
Checked
Display Periodic Inspection
HOA Keypad
• Make sure data appears on the display properly.
• Inspect for dust or other foreign material that may have
collected on surrounding components.
• Contact the nearest sales office if there is any
trouble with the display or keypad.
• Clean the HOA keypad.
u
Storage Guidelines
The drive contains electrolytic capacitors and fine electronic parts that undergo chemical changes. Observe the following
precautions to help maintain the expected performance life and reliability during long-term storage.
n
Storage Location
Temperature and Humidity
Store the drive in a location that is between -10 and +40 °C with a relative humidity of 95% or less. Do not store the drive in
direct sunlight or where condensation or ice will form.
Storage temperatures between -20 to +60 °C are allowed when storing the drive for approximately one month.
Note:
Package and store the drive during shipping to protect it from vibration and shock.
Dust and Oil Mist
Do not store the drive in a dusty location or a location subject to oil mist.
Corrosive Gas
Do not store the drive in a location subject to corrosive gas.
Salt Damage
Do not store the drive in a location subject to salt damage, such as near the ocean.
Do not store the drive in adverse environments. Store all drives in storage rooms that are not subjected to adverse environmental
elements.
Periodic Power Application
Yaskawa recommends applying power to the drive once per year for at least 30 minutes to prevent the capacitors from
deteriorating.
When applying power after power has not been applied for more than two years, Yaskawa recommends using a variable power
source and gradually increasing the power from 0 V to the rated drive voltage over a period of 2 to 3 minutes. Apply power
for at least 1 hour with no load to age the main circuit electrolytic capacitor.
Wire the drive normally and check for drive faults, overcurrents, motor vibration, speed fluctuations, and other abnormalities
during operation after performing the above procedure.
MC
Drive
R
S
T
U
V
W
Variable power source
AC supply
Figure 2.1 Power Distribution Method