No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H5-17
(11A1)
Operation Selection
when Unable to Write
into EEPROM
Busy Enter Sel
0: No ROM Enter
1: RAM Enter
Selects operation when an attempt is made to write data into
EEPROM via MEMOBUS/Modbus communications and
writing into EEPROM is not possible.
There is normally no need to change this parameter from the
default value
0: Cannot write into EEPROM
1: Write in RAM only
Default: 0
Range: 0, 1
H5-18
(11A2)
Filter Time Constant for
Motor Speed Monitoring MtrSpd Monitor T
Sets the filter time constant for monitoring the motor speed from
MEMOBUS/Modbus communications and communication
options.
Applicable MEMOBUS/Modbus registers are: 3EH, 3FH, 44H,
ACH, and ADH
Default: 0 ms
Min.: 0
Max.: 100
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
A.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
227
A
Parameter List