![YASKAWA Z1000U Series Programming Manual Download Page 209](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538209.webp)
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
E5-03
(032B)
<1>
Motor Rated Current
(for PM Motors)
PM Mtr Rated FLA
OLV/PM
OLV/PM
Sets the motor rated current.
Default:
<3>
Min: 10% of
drive rated
current
Max: 150% of
drive rated
current
<5>
E5-04
(032C)
<1>
Number of Motor Poles
(for PM Motors)
PM Motor Poles
OLV/PM
OLV/PM
Sets the number of motor poles.
Default:
<3>
Min.: 2
Max.: 48
E5-05
(032D)
<1>
Motor Stator Resistance
(for PM Motors)
PM Mtr Arm Ohms
OLV/PM
OLV/PM
Set the resistance for each motor phase.
Default:
<3>
Min.: 0.000 Ω
Max.: 65.000 Ω
E5-06
(032E)
<1>
Motor d-Axis
Inductance (for PM
Motors)
PM Mtr d Induct
OLV/PM
OLV/PM
Sets the d-Axis inductance for the PM motor.
Default:
<3>
Min.: 0.00 mH
Max.: 300.00 mH
E5-07
(032F)
<1>
Motor q-Axis
Inductance (for PM
Motors)
PM Mtr q Induct
OLV/PM
OLV/PM
Sets the q-Axis inductance for the PM motor.
Default:
<3>
Min.: 0.00 mH
Max.: 600.00 mH
E5-09
(0331)
<1>
Motor Induction Voltage
Constant 1 (for PM
Motors)
PM Mtr Ind V 1
OLV/PM
OLV/PM
Sets the induced peak voltage per phase in units of
0.1 mV/(rad/s) [electrical angle]. Set this parameter when using
an IPM motor with variable torque.
Set E5-24 to 0 when setting this parameter.
Default:
<3>
Min.: 0.0 mV/
(rad/s)
Max.: 2000.0
mV/
(rad/s)
E5-24
(0353)
<1>
Motor Induction Voltage
Constant 2 (for PM
Motors)
PM Mtr Ind V 2
OLV/PM
OLV/PM
Sets the induced phase-to-phase rms voltage in units of
0.1 mV/(r/min) [mechanical angle].
Default:
<3>
Min.: 0.0 mV/
(r/min)
Max.: 6500.0
mV/
(r/min)
<1> Setting value is not reset to the default when drive is initialized.
<2> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<3> Default setting is dependent on parameter E5-01, Motor Code Selection.
<4> Selection may vary depending on the motor code entered to E5-01.
<5> Display is in the following units:
2
o
0028, 2
o
0042, and 4
o
0011 to 4
o
0027: 0.01 A units
2
o
0054 to 2
o
0248 and 4
o
0034 to 4
o
0414: 0.1 A units
A.7 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual