S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-03
Sequence Timer 1 Day Selection
0 to 10
0
S2-08
Sequence Timer 2 Day Selection
0 to 10
0
S2-13
Sequence Timer 3 Day Selection
0 to 10
0
S2-18
Sequence Timer 4 Day Selection
0 to 10
0
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-04
Sequence Timer 1 Selection
0 to 2
0
S2-09
Sequence Timer 2 Selection
0 to 2
0
S2-14
Sequence Timer 3 Selection
0 to 2
0
S2-19
Sequence Timer 4 Selection
0 to 2
0
Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PID Disable
n
S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source
Selects the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when
S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).
Note:
H1-
oo
= 12/13 overrides these sequence timer run sources in drive software versions PRG: 1018 and later.
No.
Name
Setting Range
Default
S2-05
Sequence Timer 1 Reference Source
0 to 6
0
S2-10
Sequence Timer 2 Reference Source
0 to 6
0
S2-15
Sequence Timer 3 Reference Source
0 to 6
0
S2-20
Sequence Timer 4 Reference Source
0 to 6
0
1.11 S: Special Parameters
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
145