H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
31
PID integral hold
PID Intgrl Hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
34
PID soft starter cancel
PID SFS Cancel
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
35
PID input level selection PID Input Invert
Closed: Inverts the PID input signal.
40
Forward run command
(2-Wire sequence)
FwdRun 2Wire Seq
Open: Stop
Closed: Forward run
Note:
Cannot be set together with settings 42 or 43.
41
Reverse run command
(2-Wire sequence)
RevRun 2WireSeq
Open: Stop
Closed: Reverse run
Note:
Cannot be set together with settings 42 or 43.
42
Run command
(2-Wire sequence 2)
Run/Stp 2WireSeq
Open: Stop
Closed: Run
Note:
Cannot be set together with settings 40 or 41.
43
FWD/REV command
(2-Wire sequence 2)
FWD/REV 2WireSeq
Open: Forward
Closed: Reverse
Note:
Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
44
Offset frequency 1
Offset Freq 1
Closed: Adds d7-01 to the frequency reference.
45
Offset frequency 2
Offset Freq 2
Closed: Adds d7-02 to the frequency reference.
46
Offset frequency 3
Offset Freq 3
Closed: Adds d7-03 to the frequency reference.
47
Node setup
CanOpenNID Setup
Closed: Node setup for SI-S3 enabled.
50
Motor Pre-Heat 2
Motor Preheat 2
Closed: Triggers Motor Pre-Heat 2.
51
Sequence Timer Disable SeqTimer Disable
Closed: Drive ignores sequence timers and runs normally.
52
Sequence Timer Cancel SeqTimer Cancel
Closed: Sequence Timer Cancel .
60
Motor pre-heat 1
DCInj Activate
Closed: Triggers Motor pre-heat 1.
61
External Speed Search
command 1
Speed Search 1
Closed: Activates Current Detection Speed Search from the maximum output
frequency (E1-04).
62
External Speed Search
command 2
Speed Search 2
Closed: Activates Current Detection Speed Search from the frequency reference.
63
Field weakening
Field Weak
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
67
Communications test
mode
Comm Test Mode
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the
test completes successfully.
69
Jog 2
Jog 2
Cause the drive to ramp to the jog frequency (d1-17).
6A
Drive enable
Drive Enable
Open: Drive disabled. If this input is opened during run, the drive will stop as
specified by b1-03.
Closed: Ready for operation.
6D
AUTO mode select
AUTO Mode Sel
Legacy Operation Mode (S5-04 = 0)
• Open: HAND reference is selected (based on S5-01)
• Closed: AUTO reference is selected (based on b1-01)
Normal Operation Mode (S5-04
≠
0)
Note:
The drive will always be in AUTO mode at power up when
S5-04 is set to 1.
• Open: Drive is in OFF or HAND mode.
• Closed: Drive is in AUTO mode (when HAND mode select input is open)
6E
HAND mode select
HAND Mode Se
Legacy Operation Mode (S5-04 = 0)
• Open: AUTO reference is selected (based on b1-01)
• Closed: HAND reference is selected (based on S5-01)
Normal Operation Mode (S5-04
≠
0)
Note:
The drive will always be in AUTO mode at power up when
S5-04 is set to 1.
• Open: Drive is in OFF or AUTO mode.
• Closed: Drive is in HAND mode. (when AUTO mode select input is open)
A.9 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
219