S6: Phase Order Selections
n
S6-01: Emergency Override Speed
Sets the speed command used in emergency override mode when S6-02 = 0.
No.
Name
Setting Range
Default
S6-01
Emergency Override Speed
0.00 to [E1-04]
0.00 Hz
n
S6-02: Emergency Override Reference Selection
Selects the frequency reference source for the Emergency Override function (H1-
oo
= AF or B0). Emergency Override
ignores faults such as oL2, oH1, oL1/oL2/oL3, EF
oo
, oH1/oH3/oH4, LL3, rH, oPr, CPF, PID faults, LF/LF2, UL3, PF, and
any other faults, if possible.
No.
Name
Setting Range
Default
S6-02
Emergency Override Reference Selection
0, 1
0
Setting 0: Use S6-01 Reference
Setting 1: Use AUTO Reference
n
S6-07: Output Phase Loss Detection Level for Dynamic Audible Noise Control
Sets the output phase loss detection level for Dynamic Audible Noise Control. Decrease the setting in steps of 10% when
output phase loss is detected erroneously. This setting rarely needs to be changed.
No.
Name
Setting Range
Default
S6-07
Output Phase Loss Detection Level for Dynamic Audible Noise
Control
10.0 to 100.0%
100.0%
1.11 S: Special Parameters
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual