VS-616PS5 Installation & Quick Start Manual
Page D-5
D2
Reference Limits
D2-01 Reference upper limit
%
0.0~110.0
100.0
B
D2-02 Reference lower limit
%
0.0~100.0
0.0
B
D3
Jump Frequencies
D3-01 Jump frequency reference 1
%
0.0~200.0
0.0
A
D3-02 Jump frequency reference 2
%
0.0~200.0
0.0
A
D3-03 Jump frequency reference 3
%
0.0~200.0
0.0
A
D3-04 Jump frequency reference bandwidth
%
0.0~200.0
1.0
A
D4
Hold reference memory
D4-01 Hold reference memory selection - Up/Down
0: Disabled
1: Enabled
-
0/1
0
A
D5
Torque Control
D5-01 Torque control selection
0: Speed control
1: Torque control
-
0/1
0
A
D5-02 Torque limit primary delay time
ms
0~1000
0
A
D5-03 Speed limit input selection
1: Analog Input
2: Program Setting
-
1/2
1
A
D5-04 Speed limit value
%
±120
0
A
D5-05 Speed limit bias
%
0~120
5
A
D5-06 Reference delay time
ms
0~1000
50
A
E
Motor Parameters
E1
Motor Constant
E1-01 Input voltage setting
V
180~230
230
Q
E1-02 Motor capacity selection
-
1000~1239
1000
Q
E1-03 Motor rated voltage
V
0.0~255.0
*
Q
E1-04 Motor rated current
A
0.0~200.0
*
Q
E1-05 Number of motor poles
-
2, 4, 6, 8
*
Q
E1-06 Maximum motor speed
rpm
0~6000
*
Q
E1-07 Base motor speed
rpm
0~6000
*
Q
E1-08 Minimum motor speed
rpm
0~6000
*
Q
E1-09 Motor armature resistance
Ω
0.000~65.535
*
Q
E1-10 Motor d axis inductance
mH
0.00~600.00
*
Q
E1-11 Motor q axis inductance
mH
0.00~600.00
*
Q
E1-13 Induced voltage constant
mV/rpm
20.0~500.0
*
Q
E1-15 Motor mechanical loss
%
0.0~10.0
*
A
E1-16 Motor feeder resistance
%
0.0~10.0
*
A
E1-17 Motor connection selection
0: 1D
2: 1Y
1: 2D
3: 2Y
-
0~3
0
Q
F
Option Parameters
F1
PG Option Setup
F1-01 PG pulses per revolution
-
0~10000
30
Q
F1-02 PG disconnection detection stopping method
0: Ramp to stop
2: Fast-stop
1: Coast to stop
3: Alarm only
-
0~3
1
B
F1-03 Overspeed detection stopping method
0: Ramp to stop
2: Fast-stop
1: Coast to stop
3: Alarm only
-
0~3
1
B
No.
Parameter Description
Unit
Setting Range
Default
Access
Level
User
Setting