VS-616PS5 Installation & Quick Start Manual
Page A-1
APPENDIX A
APPENDIX A
WIRING TABLES
WIRING TABLES
A.1
Terminal Functions ....................................................................................................................A-1
230V Class Terminal Functions.................................................................................................A-1
460V Class Terminal Functions.................................................................................................A-1
A.2
Wire Sizes and Terminal Screw Sizes.......................................................................................A-2
230V Class Wire Size................................................................................................................A-2
460V Class Wire Size................................................................................................................A-3
A.3
JST Closed Loop Connectors ...................................................................................................A-4
A.1
Terminal Functions
230V Class Terminal Functions
460V Class Terminal Functions
Model CIMR-PS5U
20P4 to 27P5
2011 to 2015
Nominal Motor Output
0.5 to 10 HP
15 to 20 HP
L1, L2, L3
Main power supply input: 200 to 230 VAC, 3 Ø, 50/60 Hz
T1, T2, T3
Inverter output: 200 to 230 VAC, 3 Ø, 200 Hz max
B1, B2
Braking Resistor Unit
-
DC Power 1 to -
DC R1 to +2
DC Power 1 to -
DC R1 to +2
Braking Unit +3 to -
+ 1
+ 2
+ 3
- -
GND
Earth Ground Terminal (Resistance to earth = 100 ohms or less)
Model CIMR-PS5U
40P4 to 4015
4018 to 4045
4055 to 4160
4185 to 4300
Nominal Motor Output
0.5 to 25 HP
30 to 75 HP
100 to 200 HP
250 to 500 HP
L1, L2, L3
Main power supply input: 380 to 460 VAC, 3 Ø, 50/60 Hz
T1, T2, T3
Inverter output: 380 to 460 VAC, 3 Ø, 200 Hz max
B1, B2
Braking Resistor Unit
-
DC Power 1 to -
DC R1 to +2
DC Power 1 to -
Braking Unit +3 to -
Braking Unit +3 to –
(No +1 or +2 terminals
provided)
Braking Unit +3 to -
+ 1
+ 2
+ 3
- -
S
- -
Cooling Fan Power
Supply
- -
R
Control power Supply
R to S200: 200 to 230 VAC 1
Ø
R to S400: 380 to 460 VAC 1Ø
S200
_ _
S400
GND
Earth Ground Terminal (Resistance to earth = 10 ohms or less)