VS-616PS5 Installation & Quick Start Manual
Page D-3
Programming
B
Application
B1
Sequence
B1-01 Frequency reference selection
0: Operator
3: Option PCB
1: Terminals
4: CP-717
2: Serial communication
-
0~4
1
Q
B1-02 Operation method selection
0: Operator
3: Option PCB
1: Terminals
4: CP-717
2: Serial communication
-
0~4
1
Q
B1-03 Stopping method selection
0: Ramp to stop
3: Coast with timer
1: Coast to stop
-
0~3
0
Q
B1-04 Prohibition of reverse operation
0: Reverse enabled
1: Reverse disabled
-
0/1
0
B
B1-05 Operation selection at zero speed
0: RUN at freq. ref
2: RUN at min freq.
1: Stop
3: RUN at zero rpm
-
0~3
1
A
B1-06 Local/Remote run select
0: Cycle extra RUN
1: Accept extra RUN
-
0/1
1
A
B2
Servo Speed Level
B2-01 Zero speed level (BB starting speed)
%
0.0~20.0
0.5
B
B3
Magnetic Pull-in
B3-02 Magnetic pull-in current
%
0~150
50
A
B3-04 Current ramp-up time
s
0.0~5.0
1.0
A
B3-05 Magnetic pull-in time
s
0.0~5.0
1.0
A
B4
Delay Timers
B4-01 On-delay timer
s
0.0~300.0
0.0
A
B4-02 Off-delay timer
s
0.0~300.0
0.0
A
B5
PID Control
B5-01 PID control mode selection
0: Disabled
1: Enabled D = feedback
2: Enabled D = feedfwd
-
0~2
0
A
B5-02 PID control proportional gain
-
0.00~25.00
1.00
A
B5-03 PID control integral time
s
0.00~360.0
1.00
A
B5-04 PID control integral limit
%
0.0~100.0
100.0
A
B5-05 PID control derivative time
s
0.00~10.00
0.00
A
B5-06 PID control limit
%
0.0~100.0
100.0
A
B5-07 PID control offset
%
±100.0
0.0
A
B5-08 PID control output primary delay time
s
0.00~10.00
0.00
A
B6
Reference Hold
B6-01 Dwell reference at start (dwell level)
%
0.0~100.00
0.00
A
B6-02 Dwell time at start (dwell time)
s
0.0~10.0
0.0
A
B6-03 Dwell reference at stop (dwell level)
%
0.0~100.00
0.00
A
B6-04 Dwell time at stop (dwell time)
s
0.0~10.0
0.0
A
B7
Droop Control
B7-01 Droop capacity
%
0.0~100.0
0.0
A
B7-02 Droop delay time
s
0.00~1.00
0.10
A
No.
Parameter Description
Unit
Setting Range
Default
Access
Level
User
Setting