52
VS-616PS5 Installation & Quick Start Manual
Terminal Designation Options
When the inverter is initialized (A1-03) to “2220” (2-wire operation), terminal 1 is FWD RUN, and terminal 2 is REV
RUN. Connecting either input with a contact to terminal 11 causes the inverter to run in that direction as long as the
contact is closed, and to stop running when the contact is opened.
When the inverter is initialized (A1-03) to “3330” (3-wire operation), terminal 1 is the START input and terminal 2 is
the STOP input. The inverter runs after START is connected momentarily to terminal 11 provided STOP is already
connected to terminal 11. The inverter will continue to run until the STOP input is opened. Terminal (5) will be set to
“00” to act as a FORWARD/REVERSE input.
H1 – 01 to H1 - 06
Multifunction Input Terminals Selection
Default assignments are as follows (all contact closures are to terminal 11):
The following settings are available for the terminals. Unless otherwise indicated, closing a normally open contact
to terminal 11 activates the input terminal function.
Consult the VS-616PS5 Programming Manual for more comprehensive discussions of the parameters.
Input
Terminal
Parameter
Default
Setting
Default Function
3
H1-01
24
External Fault – close contact to trip inverter off
4
H1-02
14
Fault Reset – close contact to reset faults in inverter
5
H1-03
3
Preset Reference Selector 1 – close contact to select preset speeds
6
H1-04
4
Preset Reference Selector 2 – close contact to select preset speeds
7
H1-05
6
Jog Reference – close contact to select preset jog speed reference
8
H1-06
8
External Baseblock (N.O.) – close contact to disable inverter output
Setting
Function
0
3-wire control
The terminal set to “0” becomes the Forward/Reverse input
1
Local/Remote
Selects the operation mode (open = Local). Inverter must be stopped.
2
Internal/Option
Selects Reference source (open = internal, closed = option card)
3
Preset Reference 1
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
4
Preset Reference 2
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
5
Preset Reference 3
Selects Preset Speed Reference when closed (see D1-01 thru D1-08)
6
JOG Reference
Selects Jog Preset Reference when closed. RUN input must be active
7
Accel/Decel Select 1
Selects alternate Accel/Decel rates when closed (see C1-03 and C1-04)
8
External Baseblock NO
Disables output of inverter when contact closes
9
External Baseblock NC
Disables output of inverter when contact opens
A
Accel/Decel Ramp Hold
Stops ramping when closed, resumes ramping when opened
B
Inverter OH2 Alarm
External temperature alarm input, causes display to blink “OH2”
C
Terminal 16 Enable
Enables the analog input at terminal 16 when closed
E
ASR Integral Reset
Resets Integral control values of inverter when closed
F
No Operation
Terminal is not being used
10
MOP Increase
Accelerate while closed with MOP decrease open, otherwise no effect
11
MOP Decrease
Decelerate while closed with MOP increase open, otherwise no effect
12
Forward JOG
Run forward at Jog preset speed reference D1-09 while closed
13
Reverse JOG
Run reverse at Jog preset speed reference D1-09 while closed
14
Fault Reset
Resets Inverter faults while closed; must be opened to run again
15
Fast Stop
Causes inverter to stop at Fast Stop decel rate (C1-09)
1A
Accel/Decel Select 2
Selects alternate Accel/Decel rates when closed
1B
Program Lockout
Prohibits changing of PS5 parameters while open
1E
Reference Sample Hold
Samples frequency reference if closed for 100 ms or longer
1F
Terminal 13/14 Switch
Selects terminal 13 input (open) or terminal 14 input(closed)
24
External Fault
Shuts off inverter when closed, displays “oPE_” on operator
71
Speed/Torque Control
Selects Speed control (open) or torque control (closed)
77
ASR Gain Switch
Switches Gain values in ASR (see C5-01 / C5-02)