38
VS-616PS5 Installation & Quick Start Manual
Motor Parameters
The motor parameters must be entered before attempting operation of the motor. Motor information is obtained
from the nameplate of the motor and from Appendix B of this manual (partial listing only). Older motors do not
have all their characteristics listed on their nameplates. It may be necessary to contact the motor manufacturer to
obtain the data for programming parameters E1-03 thru E1-17.
E1 – 01
Input Voltage
Enter the nominal power supply voltage supplied to the inverter.
E1 – 02
Motor Capacity Selection
Enter “1000” for custom motor data. Entering numbers greater than 1000 access stored motor characteristics that
load most of the “E” parameters (future addition- reference Appendix B). Used in conjunction with motor connec-
tion selection, parameter E1-17, to automatically load parameters, E1-03 thru E1-13. Set E1-17 to the correct
winding configuration prior to programming E1-02 to the desired winding code.
E1 – 03
Rated Motor Voltage
Enter the motor voltage according to the nameplate bus voltage.
E1 – 04
Motor Rated Current
Enter the rated motor current (from nameplate). The maximum value that can be entered for an inverter is equal to
inverter rated current (nameplate value).
E1 – 05
Number of Motor Poles
Enter the number of motor poles according to the nameplate.
Minimum
Maximum Inverter Type
Default Setting
155
255
230V class PS5 inverter
230
310
510
460V class PS5 inverter
460
Minimum
Maximum Description
Default Setting
1000
1999
Winding number - obtained from motor model number
1000
Minimum
Maximum Inverter Type
Setting
0
255
320 VDC bus voltage motors
230
0
510
640 VDC bus voltage motors
460
Minimum
Maximum Description
Default Setting
000.00
605.0
Rated Motor Current FLA from nameplate –
7.5 Kw or less resolution 0.01A
11 Kw or more resolution 0.1A
- -
Minimum
Maximum Description
Default Setting
2
8
Winding number - obtained from motor model number
1000