4
Example of Quick Start Motor Data Entry (See page 35 for complete explanation)
Parameter
Name
Description
Example
E1-01
Input Voltage Setting
Set equal to the input supply voltage in VAC RMS
230
E1-02
Motor Capacity
Set to 1000 for manual entry of the following “E1” parameters
1000
E1-03
Rated Motor Voltage
Set to 230 for motors with 320VDC BUS on the nameplate
Set to 460 for motors with 640VDC BUS on the nameplate
230
E1-04
Motor Rated Current
Enter the motor nameplate full load current in AC Amps RMS
9.6
E1-05
Number of Poles
Set for the number of poles in motor (even number)
4
E1-06
Motor Maximum Speed
Set to the maximum speed desired being sure not to exceed the
motor maximum RPM
1750
E1-07
Base Motor Speed
Set to nameplate base speed of the motor in RPM
1750
E1-08
Minimum Motor Speed
Set to the Minimum Motor Speed
30
E1-09
Motor Winding Resistance
Set to line to line winding resistance in ohms
0.102
E1-10
Motor d-axis Inductance
Set to Stator Inductance in millihenries
5.45
E1-11
Motor q-axis Inductance
Set equal to E1-10
5.45
E1-13
Induced Voltage Constant
Set to motor Generated voltage KV in VAC RMS (V/1000 RPM)
176.0
E1-17
Motor Connection
Set to 0 = 1D, 1 = 2D, 2 = 1Y, 3 = 2Y
0
F1-01
PG Feedback Rate
Set to number of pulses in one encoder speed channel (PPR)
30
F8-01
Speed Feedback Source
Set to “1” for Hall Sensors, set to “0” for encoder feedback
01