background image

SM-DIO | | Manual

HB140 | SM-DIO | | en | Rev. 16-43

VIPA System 300S

Digital signal modules - SM 32x(S)

www.vipa.com/en/service-support/manual

Summary of Contents for VIPA System 300S

Page 1: ...SM DIO Manual HB140 SM DIO en Rev 16 43 VIPA System 300S Digital signal modules SM 32x S www vipa com en service support manual ...

Page 2: ...300S_SM DIO 4 GB 2016 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 09132 744 0 Fax 09132 744 1864 Email info vipa com Internet www vipa com ...

Page 3: ...fe shutdown of non safe outputs 35 4 1 1 Introduction 35 4 1 2 Safe shutdown 35 4 1 3 Requirements and fault exclusions 36 4 2 322 1BF01 DO 8xDC 24V 2A 38 4 2 1 Technical data 39 4 3 322 1BH01 DO 16xDC 24V 1A 41 4 3 1 Technical data 43 4 4 322 1BH41 DO 16xDC 24V 2A 45 4 4 1 Technical data 48 4 5 322 1BH60 DO 16xDC 24V 0 5A for manual operation 50 4 5 1 Deployment 52 4 5 2 Technical data 52 4 6 322...

Page 4: ...3 Steps of project engineering 87 6 3 321 1BH70 DI 16xDC 24V 89 6 3 1 Parameterization 92 6 3 2 Process interrupt 96 6 3 3 Diagnostic interrupt 97 6 3 4 Technical data 100 6 4 322 1BH70 DO 16xDC 24V 0 5A 102 6 4 1 Technical data 105 6 5 323 1BH70 DIO 16xDC 24V 0 5A 106 6 5 1 Parameterization 109 6 5 2 Process interrupt 114 6 5 3 Diagnostic interrupt 114 6 5 4 Technical data 117 VIPA System 300S Ta...

Page 5: ...ctive purchase contract Hereby VIPA GmbH declares that the products and systems are in compliance with the essential requirements and other relevant provisions Conformity is indicated by the CE marking affixed to the product For more information regarding CE marking and Declaration of Conformity DoC please contact your local VIPA customer service organization VIPA SLIO System 100V System 200V Syst...

Page 6: ... chapters Every chapter provides a self contained description of a specific topic The following guides are available in the manual n An overall table of contents at the beginning of the manual n References with page numbers The manual is available in n printed form on paper n in electronic form as PDF file Adobe Acrobat Reader Important passages in the text are highlighted by following icons and h...

Page 7: ...department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the components described in this manual Hardware modifications to the process control system should only be carried out when the system has been disconnected from power Installation and hardware modifications only by properly trained per sonnel The national rules and regulations of th...

Page 8: ...s that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices and meticulous attention to the applicable rules and regulations for handling the respective equipment can prevent failures of electrostatic sensitive modules Modules must be shipped in the original pack...

Page 9: ...s With SPEED Bus the bus connection happens via a SPEED Bus rail integrated in the profile rail at the left side of the CPU Due to the parallel SPEED Bus not all slots must be occupied in sequence At slot SLOT 1 DCDC you may plug either a SPEED Bus module or an additional power supply You may assemble the System 300 horizontally vertically or lying Please regard the allowed environment temperature...

Page 10: ...Dimensions Installation dimensions VIPA System 300S Assembly and installation guidelines Installation dimensions HB140 SM DIO en Rev 16 43 10 ...

Page 11: ...f modules SPEED Bus Standard bus A B C D E 391 1AF10 2 6 530 100 268 510 10 391 1AF30 6 2 530 100 105 510 10 391 1AF50 10 0 530 20 20 510 10 391 1AJ10 2 15 830 22 645 800 15 391 1AJ30 6 11 830 22 480 800 15 391 1AJ50 10 7 830 22 320 800 15 Measures in mm Pre manufactured SPEED Bus profile rail Dimensions VIPA System 300S Assembly and installation guidelines Assembly SPEED Bus HB140 SM DIO en Rev 1...

Page 12: ...laps of the SPEED Bus slot with a screw driver open and pull down For the SPEED Bus is a parallel bus not every SPEED Bus slot must be used in series Leave the protection flap installed at an unused SPEED Bus slot 2 At deployment of a DC 24V power supply install it at the shown position at the pro file rail at the left side of the SPEED Bus and push it to the left to the isolation bolt of the prof...

Page 13: ...e shown in the picture Plug the CPU between the triangular positioning helps to the slot marked with CPU SPEED7 and pull it down 2 Plug the CPU between the triangular positioning helps to the plug in location marked with CPU SPEED7 and pull it down Fix the CPU by screwing Repeat this procedure with the peripheral modules by clicking a backplane bus coupler stick the module right from the modules y...

Page 14: ...y installed on a profile rail and connected via the backplane bus connector Before installing the modules you have to clip the backplane bus con nector to the module from the backside The backplane bus connector is delivered together with the peripheral modules Order number A B C 390 1AB60 160 140 10 390 1AE80 482 466 8 3 390 1AF30 530 500 15 390 1AJ30 830 800 15 390 9BC00 2000 Drillings only left...

Page 15: ...rail 2 If the background is a grounded metal or device plate please look for a low impe dance connection between profile rail and background 3 Connect the profile rail with the protected earth conductor For this purpose there is a bolt with M6 thread 4 The minimum cross section of the cable to the protected earth conductor has to be 10mm2 5 Stick the power supply to the profile rail and pull it to...

Page 16: ... bus connector of the last module and bolt it 2 6 Cabling CAUTION The power supplies must be released before installation and repair tasks i e before handling with the power supply or with the cabling you must disconnect current voltage pull plug at fixed connection switch off the concerning fuse Installation and modifications only by properly trained personnel VIPA System 300S Assembly and instal...

Page 17: ...ture on the left side shows the cabling step by step from top view 1 For cabling you push the locking vertical to the inside with a suiting screwdriver and hold the screwdriver in this position 2 Insert the de isolated wire into the round opening You may use wires with a cross section from 0 08mm2 to 2 5mm2 3 By removing the screwdriver the wire is connected safely with the plug connector via a sp...

Page 18: ...tom to top res from top to bottom if the cables should be led out at the top 6 Bolt also the connection screws of not cabled screw clamps 7 Fix the cable binder for the cable bundle 8 Push the release key at the front connector on the upper side of the module and at the same time push the front connector into the module until it locks 9 Now the front connector is electrically connected with your m...

Page 19: ... the cable bundle and the front connector 7 Fix the cable binder for the cable bundle 8 Bolt the fixing screw of the front connector 9 Now the front connector is electrically connected with your module 10 Close the front flap 11 Fill out the labeling strip to mark the single channels and push the strip into the front flap 2 7 Installation guidelines The installation guidelines contain information ...

Page 20: ... when installing your components Install a central connection between the ground and the protected earth conductor system Connect all inactive metal extensive and impedance low Please try not to use aluminium parts Aluminium is easily oxidizing and is there fore less suitable for grounding n When cabling take care of the correct line routing Organize your cabling in line groups high voltage curren...

Page 21: ...the both sided connection of the isolation you achieve high quality interference suppression in the higher frequency area Only as exception you may also lay the iso lation one sided Then you only achieve the absorption of the lower frequencies A one sided isolation connection may be convenient if the conduction of a potential compensating line is not possible analog signals some mV respectively µA...

Page 22: ...ion IP20 Electrical isolation to the field bus electrically isolated to the process level electrically isolated Insulation resistance Insulation voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14 25 70 C Operation Horizontal installation hanging EN 61131 2...

Page 23: ...ntact discharge degree of severity 2 EN 61000 4 3 HF field immunity casing 80MHz 1000MHz 10V m 80 AM 1kHz 1 4GHz 2 0GHz 3V m 80 AM 1kHz 2GHz 2 7GHz 1V m 80 AM 1kHz EN 61000 4 6 HF conducted 150kHz 80MHz 10V 80 AM 1kHz EN 61000 4 4 Burst degree of severity 3 EN 61000 4 5 Surge installation class 3 Due to the high energetic single pulses with Surge an appropriate external protective circuit with lig...

Page 24: ...6 channels and their status is monitored via LEDs n 16 inputs isolated to the backplane bus n Nominal input voltage DC 24V n Useable for switches and approximate switches n Status monitoring of the channels via LED 1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Properties Structure VIPA System 300S Digital Input Modules 321 1BH01 DI 16xDC 24V HB140 SM DIO en Rev 16 ...

Page 25: ...ng LED is activated 2 Input I 0 0 9 Input I 0 7 12 Input I 1 0 19 Input I 1 7 20 Ground 3 1 1 Technical data Order no 321 1BH01 Type SM 321 SPEED Bus Current consumption power loss Current consumption from backplane bus 25 mA Power loss 3 5 W Technical data digital inputs Schematic diagram VIPA System 300S Digital Input Modules 321 1BH01 DI 16xDC 24V Technical data HB140 SM DIO en Rev 16 43 25 ...

Page 26: ...of simultaneously utilizable inputs horizontal con figuration 16 Number of simultaneously utilizable inputs vertical configu ration 16 Input characteristic curve IEC 61131 2 type 1 Initial data size 2 Byte Status information alarms diagnostics Status display green LED per channel Interrupts no Process alarm no Diagnostic interrupt no Diagnostic functions no Diagnostics information read out none Su...

Page 27: ...ication yes KC certification yes 3 2 321 1BL00 DI 32xDC 24V The digital input module collects the binary control signals from the process level and transmits them isolated to the superordinate bus system It has 32 channels and their status is monitored via LEDs n 32 inputs isolated to the backplane bus n Nominal input voltage DC 24V n Useable for switches and approximate switches n Status monitori...

Page 28: ... Description 1 not used 0 7 LEDs green I 0 0 to I 3 7 from ca 15V on the signal is recognized as 1 and the according LED is acti vated 2 9 Input I 0 0 I 0 7 12 19 Input I 1 0 I 1 7 20 Ground 21 not used 22 29 Input I 2 0 I 2 7 32 39 Input I 3 0 I 3 7 40 Ground Structure VIPA System 300S Digital Input Modules 321 1BL00 DI 32xDC 24V HB140 SM DIO en Rev 16 43 28 ...

Page 29: ...ength shielded 1000 m Cable length unshielded 600 m Rated load voltage Current consumption from load voltage L without load Rated value DC 20 4 28 8 V Input voltage for signal 0 DC 0 5 V Input voltage for signal 1 DC 15 28 8 V Input voltage hysteresis Frequency range Schematic diagram Numeric representation VIPA System 300S Digital Input Modules 321 1BL00 DI 32xDC 24V Technical data HB140 SM DIO e...

Page 30: ...ostics Status display green LED per channel Interrupts no Process alarm no Diagnostic interrupt no Diagnostic functions no Diagnostics information read out none Supply voltage display none Group error display none Channel error display none Isolation Between channels Between channels of groups to 16 Between channels and backplane bus ü Insulation tested with DC 500 V Datasizes Input bytes 4 Output...

Page 31: ... from the process level and transmits them isolated to the superordinate bus system It has 16 channels and their status is monitored via LEDs n 16 inputs isolated in groups of 4 n Rated input voltage AC 120 230V n Useable for switches n Status monitoring of the channels via LED 1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Properties Structure VIPA System 300S Digi...

Page 32: ... LED is activated 2 Input I 0 0 3 Input I 0 1 4 Input I 0 2 5 Input I 0 3 6 Input I 0 4 7 Input I 0 5 8 Input I 0 6 9 Input I 0 7 10 Neutral conductor 11 Neutral conductor 12 Input I 1 0 13 Input I 1 1 14 Input I 1 2 15 Input I 1 3 16 Input I 1 4 17 Input I 1 5 18 Input I 1 6 19 Input I 1 7 20 Neutral conductor Schematic diagram VIPA System 300S Digital Input Modules 321 1FH00 DI 16xAC120 230V HB1...

Page 33: ...esistance Input current for signal 1 7 mA Connection of Two Wire BEROs possible ü Max permissible BERO quiescent current 1 5 mA Input delay of 0 to 1 25 ms Input delay of 1 to 0 25 ms Number of simultaneously utilizable inputs horizontal con figuration 16 Number of simultaneously utilizable inputs vertical configu ration 16 Input characteristic curve Initial data size 2 Byte Status information ala...

Page 34: ... Output bytes 0 Parameter bytes 0 Diagnostic bytes 0 Housing Material PPE Mounting Rail System 300 Mechanical data Dimensions WxHxD 40 mm x 125 mm x 120 mm Weight 240 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes VIPA System 300S Digital Input Modules 321 1FH00 DI 16xAC120 230V Technical data H...

Page 35: ...2 1BL00 SM 322 DO 32xDC 24V 1A 4 Ä 54 323 1BL00 SM 323 DI 16xDC 24V DO 16xDC 24V 1A 5 Ä 80 After emergency shutdown according to Ä 4 1 2 safe shutdown is ensured even if the following error scenarios occur n Overvoltage on the control side n Short circuit by a power supply on the field side n Short circuit on the field side within a group n Failure of components in the module 4 1 2 Safe shutdown T...

Page 36: ...round since otherwise a two pole disconnec tion by the safety switch is not possible n The place of installation for the device is a cabinet with degree of protection IP54 or better n The installation and connection of the cables must be in accordance to EN 60204 1 and comply with the measures of EN ISO 13849 2 table D 4 If multiple power sup plies are collected to a multi conductor cable which ar...

Page 37: ...t be complied with in the DO modules developed for this pur pose Do not change the prerequisites for this fault exclusions Fault exclusion according to EN ISO 13849 2 D 5 short circuit between adjacent con ductors contact points justified by Basic material at least EP GC according to IEC60893 1 Power supply with SELV PELV Degree of pollution 2 Overvoltage category III double insulation Clearances ...

Page 38: ...eir status is monitored via LEDs n 8 outputs potential separated to the back panel bus n supply voltage DC 24V output voltage 2A n useable for magnetic valve and DC contactor n LEDs for supply voltage and error messages n Status monitoring of the channels via LED 1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Properties Structure VIPA System 300S Digital Output Modu...

Page 39: ... 1 F LED red Error when overload or short circuits 7 Output Q 0 2 9 Output Q 0 3 10 Ground 1 11 Supply voltage DC 24V 2L 13 Output Q 0 4 15 Output Q 0 5 17 Output Q 0 6 19 Output Q 0 7 20 Ground 2 4 2 1 Technical data Order no 322 1BF01 Type SM 322 SPEED Bus Current consumption power loss Current consumption from backplane bus 65 mA Power loss 7 5 W Schematic diagram VIPA System 300S Digital Outpu...

Page 40: ...r increased power possible only outputs group Actuation of digital input ü Switching frequency with resistive load max 1000 Hz Switching frequency with inductive load max 0 5 Hz Switching frequency on lamp load max 10 Hz Internal limitation of inductive shut off voltage L 52 V Short circuit protection of output yes electronic Trigger level 3 A Number of operating cycle of relay outputs Switching c...

Page 41: ... The digital output module collects the binary control signals from the superordinate bus system and transmits them isolated to the process level The module has to be provided with 24V via the front slot It has 16 channels and their status is monitored via LEDs n 16 outputs potential separated to the back panel bus n supply voltage DC 24V output voltage 1A n useable for magnetic valve and DC conta...

Page 42: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Structure VIPA System 300S Digital Output Modules 322 1BH01 DO 16xDC 24V 1A HB140 SM DIO en Rev 16 43 42 ...

Page 43: ...ted 2 Output Q 0 0 F LED red Error when overload or short circuits 9 Output Q 0 7 10 Ground 1 11 Supply voltage DC 24V 2L 12 Output Q 1 0 19 Output Q 1 7 20 Ground 2 4 3 1 Technical data Order no 322 1BH01 Type SM 322 SPEED Bus Current consumption power loss Current consumption from backplane bus 110 mA Power loss 4 W Schematic diagram VIPA System 300S Digital Output Modules 322 1BH01 DO 16xDC 24V...

Page 44: ...uts for increased power not possible Actuation of digital input ü Switching frequency with resistive load max 1000 Hz Switching frequency with inductive load max 0 5 Hz Switching frequency on lamp load max 10 Hz Internal limitation of inductive shut off voltage L 45 V Short circuit protection of output yes electronic Trigger level 1 5 A Number of operating cycle of relay outputs Switching capacity...

Page 45: ...rtifications UL certification yes KC certification yes 4 4 322 1BH41 DO 16xDC 24V 2A The digital output module collects the binary control signals from the superordinate bus system and transmits them isolated to the process level The module has to be provided with 24V via the front slot It has 16 channels and their status is monitored via LEDs n 16 outputs potential separated to the back panel bus...

Page 46: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Structure VIPA System 300S Digital Output Modules 322 1BH41 DO 16xDC 24V 2A HB140 SM DIO en Rev 16 43 46 ...

Page 47: ...As soon as an output is active the according LED is turned on 2 Output Q 0 0 F LED red Error when overload or short circuits 9 Output Q 0 7 10 Ground 1 11 Supply voltage DC 24V 2L 12 Output Q 1 0 19 Output Q 1 7 20 Ground 2 Project engineering as 322 1BH01 Schematic diagram Project engineering VIPA System 300S Digital Output Modules 322 1BH41 DO 16xDC 24V 2A HB140 SM DIO en Rev 16 43 47 ...

Page 48: ...µs Minimum load current Lamp load 10 W Parallel switching of outputs for redundant control of a load possible only outputs group Parallel switching of outputs for increased power possible only outputs group Actuation of digital input ü Switching frequency with resistive load max 1000 Hz Switching frequency with inductive load max 0 5 Hz Switching frequency on lamp load max 10 Hz Internal limitatio...

Page 49: ...plane bus ü Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 2 Parameter bytes 0 Diagnostic bytes 0 Housing Material PPE Mounting Rail System 300 Mechanical data Dimensions WxHxD 40 mm x 125 mm x 120 mm Weight 230 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes VIPA System 300...

Page 50: ...al separated to the back panel bus n 1 input potential separated for activation of all outputs n 3 setting switch per channel automatic manual 0 and manual 1 n 16 inputs switch status via input word n supply voltage DC 24V output voltage 0 5A n LEDs for supply voltage and error messages n Status monitoring of the channels via LED 1 LEDs 2 flap with labeling strip 3 switch bar 4 contact bar 5 flap ...

Page 51: ...0 0 0 7 LEDs green Q 0 0 to Q 1 7 As soon as an output is active the according LED is turned on F LED red Error when overload or short circuits 9 Output Q 0 7 10 Input for Q x 1 11 n c 12 Output Q 1 0 19 Output O 1 7 20 Ground Schematic diagram VIPA System 300S Digital Output Modules 322 1BH60 DO 16xDC 24V 0 5A for manual operation HB140 SM DIO en Rev 16 43 51 ...

Page 52: ...ot be evaluated by the PLC user program Project engineering as 323 1BL00 4 5 2 Technical data Order no 322 1BH60 Type SM 322 SPEED Bus Current consumption power loss Current consumption from backplane bus 100 mA Power loss 6 W Technical data digital outputs Number of outputs 16 Cable length shielded 1000 m Cable length unshielded 600 m Rated load voltage DC 24 V Current consumption from load volta...

Page 53: ...voltage L 52 V Short circuit protection of output yes electronic Trigger level 1 A Number of operating cycle of relay outputs Switching capacity of contacts Output data size 2 Byte Status information alarms diagnostics Status display green LED per channel Interrupts no Process alarm no Diagnostic interrupt no Diagnostic functions no Diagnostics information read out none Supply voltage display gree...

Page 54: ...te bus system and transmits them isolated to the process level The module has to be provided with 24V via the front slot It has 16 channels and their status is monitored via LEDs n 32 outputs potential separated to the back panel bus n Supply voltage DC 24V n Output voltage 1A per channel n Useable for magnetic valve and DC contactor n LEDs for supply voltage and error messages n Activity LED per ...

Page 55: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Structure VIPA System 300S Digital Output Modules 322 1BL00 DO 32xDC 24V 1A HB140 SM DIO en Rev 16 43 55 ...

Page 56: ...tive the according LED is turned on 1 3F 2 4F LED red Error when overload or short circuits 9 Output Q 0 7 10 Ground 1 11 Supply voltage 2L 12 Output Q 1 0 19 Output Q 1 7 20 Ground 2 21 Supply voltage 3L 22 Output Q 2 0 29 Output Q 2 7 30 Ground 3 31 Supply voltage 4L 32 Output Q 3 0 39 Output Q 3 7 40 Ground 4 Schematic diagram VIPA System 300S Digital Output Modules 322 1BL00 DO 32xDC 24V 1A HB...

Page 57: ...gital outputs Number of outputs 32 Cable length shielded 1000 m Cable length unshielded 600 m Rated load voltage DC 24 V Current consumption from load voltage L without load 30 mA Total current per group horizontal configuration 40 C 2 5 A Total current per group horizontal configuration 60 C 2 5 A Total current per group vertical configuration 2 5 A Output current at signal 1 rated value 1 A Outp...

Page 58: ...ching capacity of contacts Output data size 4 Byte Status information alarms diagnostics Status display green LED per channel Interrupts no Process alarm no Diagnostic interrupt no Diagnostic functions no Diagnostics information read out none Supply voltage display green LED per group Group error display red SF LED Channel error display none Isolation Between channels ü Between channels of groups ...

Page 59: ...he superordinate bus system and transmits them isolated to the process level It has 8 channels and their status is monitored via LEDs n 8 outputs isolated between the channels and to the back plane bus n Rated load voltage AC 120 230V n Output current per channel 2A n Suitable for AC solenoid valves contactors motor starters fractional h p motors and indicator lights n Group error display n Channe...

Page 60: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Structure VIPA System 300S Digital Output Modules 322 5FF00 DO 8xAC 120 230V 2A HB140 SM DIO en Rev 16 43 60 ...

Page 61: ...ltage 2L 0 7 LED green Q 0 0 to Q 0 7 As soon as an output is active the according LED is turned on 10 Q 0 1 11 Rated load voltage 3L 14 Q 0 2 17 Rated load voltage 4L 20 Q 0 3 21 Rated load voltage 5L 24 Q 0 4 27 Rated load voltage 6L 30 Q 0 5 31 Rated load voltage 7L 34 Q 0 6 37 Rated load voltage 8L 40 Q 0 7 Schematic diagram VIPA System 300S Digital Output Modules 322 5FF00 DO 8xAC 120 230V 2A...

Page 62: ...rameter window appears as soon as you double click on the according module At this window the according parameter can be changed 6 Save your project switch the CPU to STOP and transfer your project to the CPU As soon as the CPU is switched to RUN the parameters are transferred to the con nected modules The following parameters can be adjusted at the digital output modules n Reaction at CPU STOP n ...

Page 63: ...rameters in byte 0 Hold last valid value and Enable substitute value as an alternative Here the module reaction at CPU STOP may be set There are the following possibilities n Keep last valid value The value of each channel is frozen when the CPU is stopped n Substitute a value At CPU STOP each channel is substituted by a value which may be assigned by byte 1 4 7 2 Technical data Order no 322 5FF00...

Page 64: ...itching frequency with inductive load max 0 5 Hz Switching frequency on lamp load max 1 Hz Internal limitation of inductive shut off voltage Short circuit protection of output Fuse 3 15 A 250 V quick response Trigger level 3 15 A Number of operating cycle of relay outputs Switching capacity of contacts Output data size 1 Byte Status information alarms diagnostics Status display green LED per chann...

Page 65: ...relay output module collects the binary control signals from the superordinate bus system and transmits them via relay outputs to the process level The module electronics are provided via the back panel bus It has 16 channels working as switches and their status is monitored via LEDs n 16 relay outputs in groups of 8 n Power supply via back panel bus n Load capacity voltage AC 230V DC 30V n Maxima...

Page 66: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Structure VIPA System 300S Digital Output Modules 322 1HH00 DO 16xRelay HB140 SM DIO en Rev 16 43 66 ...

Page 67: ...as an output is active the according LED is turned on 2 Relay Output Q 0 0 9 Relay Output Q 0 7 10 L DC 24V 11 2L1 12 Relay Output Q 1 0 19 Relay Output Q 1 7 20 Ground When using inductive load please take an suitable protector Schematic diagram VIPA System 300S Digital Output Modules 322 1HH00 DO 16xRelay HB140 SM DIO en Rev 16 43 67 ...

Page 68: ...ion 40 C 8 A Total current per group horizontal configuration 60 C 8 A Total current per group vertical configuration 8 A Output current at signal 1 rated value 5 A Output delay of 0 to 1 10 ms Output delay of 1 to 0 5 ms Minimum load current Lamp load 6 W Parallel switching of outputs for redundant control of a load not possible Parallel switching of outputs for increased power not possible Actua...

Page 69: ...cs information read out none Supply voltage display none Group error display none Channel error display none Isolation Between channels ü Between channels of groups to 8 Between channels and backplane bus ü Insulation tested with AC 1500 V Datasizes Input bytes 0 Output bytes 2 Parameter bytes 0 Diagnostic bytes 0 Housing Material PPE Mounting Rail System 300 Mechanical data Dimensions WxHxD 40 mm...

Page 70: ...Order no 322 1HH00 Certifications UL certification yes KC certification yes VIPA System 300S Digital Output Modules 322 1HH00 DO 16xRelay Technical data HB140 SM DIO en Rev 16 43 70 ...

Page 71: ...DC 24V n Output current 1A n LED for error message at overload overheat or short circuit n Activity monitoring of the channels via LED 1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label CAUTION Please regard that the voltage applied to an output channel must be the voltage supply applied to L Due to the parallel connection of in and output channel per group a set output...

Page 72: ...Supply voltage DC 24V 2L 12 In Output I Q 1 0 0 7 LED green per Byte As soon as an input signal 1 or an active output is recognized the according LED is activated 19 In Output I Q 1 7 F LED red error at overload or short circuit 20 Ground 2 Project Engineering as 323 1BL00 Schematic diagram Project Engineering VIPA System 300S Digital Input Output Modules 323 1BH00 DIO 16xDC 24V 1A HB140 SM DIO en...

Page 73: ...n of Two Wire BEROs possible ü Max permissible BERO quiescent current 1 5 mA Input delay of 0 to 1 3 ms Input delay of 1 to 0 3 ms Number of simultaneously utilizable inputs horizontal con figuration 16 Number of simultaneously utilizable inputs vertical configu ration 16 Input characteristic curve IEC 61131 2 type 1 Initial data size 2 Byte Technical data digital outputs Number of outputs 16 Cabl...

Page 74: ...ectronic Trigger level 1 5 A Number of operating cycle of relay outputs Switching capacity of contacts Output data size 2 Byte Status information alarms diagnostics Status display green LED per channel Interrupts no Process alarm no Diagnostic interrupt no Diagnostic functions no Diagnostics information read out none Supply voltage display green LED per group Group error display red SF LED Channel...

Page 75: ...le has 16 channels isolated to the back panel bus where 8 working as inputs and the 8 working as outputs The status of the channels is shown via LEDs n 16 channels from this 8 inputs and 8 outputs n Nominal input voltage DC 24V n Supply voltage DC 24V external for outputs n Output current 1A per channel n LED for error message at overload overheat or short circuit n Activity monitoring of the chan...

Page 76: ...o the parallel connection of in and output channel per group a set output channel may be supplied via an applied input signal Thus a set output remains active even at power off of the voltage supply with the applied input signal Non observance may cause module demolition Structure VIPA System 300S Digital Input Output Modules 323 1BH01 DI 8xDC 24V DO 8xDC 24V 1A HB140 SM DIO en Rev 16 43 76 ...

Page 77: ... 10 Ground 1M inputs F LED red error at overload short circuit 11 Supply voltage DC 24V 2L 12 Output Q 0 0 19 Output Q 0 7 20 Ground 2M outputs 5 2 1 Technical data Order no 323 1BH01 Type SM 323 SPEED Bus Current consumption power loss Current consumption from backplane bus 70 mA Power loss 4 W Technical data digital inputs Schematic diagram VIPA System 300S Digital Input Output Modules 323 1BH01...

Page 78: ...y utilizable inputs vertical configu ration 8 Input characteristic curve IEC 61131 2 type 1 Initial data size 1 Byte Technical data digital outputs Number of outputs 8 Cable length shielded 1000 m Cable length unshielded 600 m Rated load voltage DC 24 V Reverse polarity protection of rated load voltage ü Current consumption from load voltage L without load 15 mA Output current at signal 1 rated va...

Page 79: ...o Process alarm no Diagnostic interrupt no Diagnostic functions no Diagnostics information read out none Supply voltage display green LED per group Group error display red SF LED Channel error display none Isolation Between channels ü Between channels of groups to 8 Between channels and backplane bus ü Insulation tested with DC 500 V Datasizes Input bytes 1 Output bytes 1 Parameter bytes 0 Diagnos...

Page 80: ...puts n Nominal input voltage DC 24V n Supply voltage DC 24V external for outputs n Output current 1A per channel n LED for error message at overload overheat or short circuit n Activity monitoring of the channels via LED n Starting from hardware version 5 safe shutdown is supported Ä Chapter 4 1 Safe shutdown of non safe outputs on page 35 1 LEDs 2 flap with labeling strip 3 contact bar 4 flap ope...

Page 81: ...odule demolition Pin assignment Circuit diagram Status monitor Pin Assignment Circuit diagram LED Description 1 Not used 1L 2L LED green supply voltage is on 2 Input I 0 0 0 7 LED green I 0 0 I 1 7 Q 0 0 Q 1 7 At signal 1 input res active output the according LED is acti vated F LED red error at overload short circuit 19 Input I 1 7 20 Ground 1M inputs 21 31 Supply voltage DC 24V 22 Output Q 0 0 3...

Page 82: ...oltage for signal 1 DC 15 28 8 V Input voltage hysteresis Frequency range Input resistance Input current for signal 1 7 mA Connection of Two Wire BEROs possible ü Max permissible BERO quiescent current 1 5 mA Input delay of 0 to 1 3 ms Input delay of 1 to 0 3 ms Number of simultaneously utilizable inputs horizontal con figuration 16 Number of simultaneously utilizable inputs vertical configu ratio...

Page 83: ...ncy with resistive load max 1000 Hz Switching frequency with inductive load max 0 5 Hz Switching frequency on lamp load max 10 Hz Internal limitation of inductive shut off voltage L 52 V Short circuit protection of output yes electronic Trigger level 1 5 A Number of operating cycle of relay outputs Switching capacity of contacts Output data size 2 Byte Status information alarms diagnostics Status ...

Page 84: ...0 Housing Material PPE Mounting Rail System 300 Mechanical data Dimensions WxHxD 40 mm x 125 mm x 120 mm Weight 260 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes VIPA System 300S Digital Input Output Modules 323 1BL00 DI 16xDC 24V DO 16xDC 24V 1A Technical data HB140 SM DIO en Rev 16 43 84 ...

Page 85: ...age To define addresses a hardware configuration via a virtual PROFIBUS system by including the SPEEDBUS GSD may be used For this click on the properties of the according module and set the wanted address If you do not like to use a hardware configuration an automatic addressing comes into force At the automatic address allocation DIOs are mapped depending on the slot loca tion with a distance of ...

Page 86: ...P master CP 342 5 342 5DA02 V5 0 as last module To this master system you assign every SPEED Bus module as VIPA_SPEEDbus slave Here the PROFIBUS address corresponds to the slot number beginning with 100 for the CPU Place at slot 0 of every slave the assigned module and alter the parameters if needed 6 2 2 Preconditions The hardware configurator is part of the Siemens SIMATIC manager It serves for ...

Page 87: ...A_System_300S and select SPEEDBUS GSD an ð The SPEED7 CPUs and modules of the System 300S from VIPA may now be found in the hardware catalog at PROFIBUS DP Additional field devices I O VIPA_SPEEDBUS 6 2 3 Steps of project engineering The following text describes the approach of the project engineering in the hardware con figurator from Siemens at an abstract sample The project engineering is separ...

Page 88: ...slot assignment of the SPEED Bus modules and the parameterization of the in output periphery happens via a virtual PROFIBUS DP master system For this place as last module a DP master 342 5DA02 V5 0 with master system For the employment of the System 300S modules at the SPEED Bus the inclusion of the System 300S modules into the hardware catalog via the GSD file speedbus gsd from VIPA is required A...

Page 89: ...ystem It has 16 chan nels and their status is monitored via LEDs n 16 fast input channels isolated to SPEED Bus n Extended parameterization possibility n Nominal input voltage DC 24V n Useable for switches and approximate switches n Status monitoring of the channels via LEDs Properties VIPA System 300S Digital Modules FAST SPEED Bus 321 1BH70 DI 16xDC 24V HB140 SM DIO en Rev 16 43 89 ...

Page 90: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Construction VIPA System 300S Digital Modules FAST SPEED Bus 321 1BH70 DI 16xDC 24V HB140 SM DIO en Rev 16 43 90 ...

Page 91: ... green I 0 0 to I 1 7 from ca 15V on the signal is recognized as 1 and the according LED is addressed 2 Input I 0 0 9 Input I 0 7 10 not used 11 not used 12 Input I 1 0 19 Input I 1 7 20 Ground Schematic diagram VIPA System 300S Digital Modules FAST SPEED Bus 321 1BH70 DI 16xDC 24V HB140 SM DIO en Rev 16 43 91 ...

Page 92: ...following parameters are at your disposal n Diagnostic interrupt global for all inputs n Edge selection switchable process interrupt per channel n Time stamp activation of a time stamp function per channel n Filter value for grubby input signals per channel During the parameterization a parameter area of 66byte is transferred in the record sets 7Fh 80h and 81h Using the SFCs 55 56 and 57 you may a...

Page 93: ...rocess image of the module at according edge Thus allows you to compare times of different input channels via your user application Via the parameter Time stamp you may activate the ETS system and define the edge of the input signal that initiates the process image entry of a time stamp You have the fol lowing options n No time stamp n Time stamp at ascending edge n Time stamp at descending edge n...

Page 94: ...ilters you may e g filter signal peaks at a blurred input signal The entry happens as a factor of 2 56µs 2 56µs 40ms and is within the range 1 16000 The record set has the following structure Word 0 Input filter I 0 0 in 2 56µs steps 30 Input filter I 1 7 in 2 56µs steps The module occupies 48byte in the input address range of the CPU that have the fol lowing meaning Byte Bit 7 Bit 0 0 State of th...

Page 95: ... Bit 7 Status I 0 7 9 Edge lost n Bit 0 Status I 1 0 n n Bit 7 Status I 1 7 10 11 reserved The following bytes contain the values of the µs ticker for a channel at the time of an edge change Only the lower 16bit are taken over An overflow after 65ms has to be accordingly processed in the user application Byte 3 2 1 0 12 Time stamp I 0 1 Time stamp I 0 0 16 Time stamp I 0 3 Time stamp I 0 2 20 Time...

Page 96: ... 0 FA1 4 0 1 1 0 0 0 1 0 0 1 0 1 1 1 1 0 FV 8 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0 FA2 44 0 0 1 1 0 0 0 0 0 0 0 1 0 0 1 0 The consistent µs ticker entries can be determined by logical bit operations FA1 AND NOT FA2 Result bit operation 0 1 0 0 0 0 1 0 0 1 0 0 0 1 0 0 Depending to the system the SFC 14 DPRD_DAT Read consistent data cannot be used with this module 6 3 2 Process interrupt Via the edge sel...

Page 97: ...r events are occurring at other channels that may also cause a process res diagnostic interrupt these are interim stored After the end of the diagnostic interrupt pro cessing at first all interim stored diagnostic interrupts are processed in the sequence of their occurrence and then all process interrupts If a channel where currently a diagnostic interruptincoming is processed res interim stored i...

Page 98: ...upt is not longer pos sible The record sets of the diagnostic range have the following structure Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 0 fix n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set when external auxiliary supply is missing n Bit 7 5 0 fix 1 n Bit 3 0 Module class 1111b Digital n Bit 4 Channel information present n Bit 7 5 0 fix 2 00h fix 3 n Bit 5 0 0 ...

Page 99: ...4 n Bit 6 0 channel type here 70h 70h Digital input n Bit 7 More channel types present n 0 no n 1 yes 5 Number of diagnostic bits the module puts out per channel here 08h 6 Number of channels of a module here 04h 7 n Bit 0 Error in channel group 0 I 0 0 I 0 3 n Bit 1 Error in channel group 1 I 0 4 I 0 7 n Bit 2 Error in channel group 2 I 1 0 I 1 3 n Bit 3 Error in channel group 3 I 1 4 I I 7 n Bit...

Page 100: ...pt lost at n Bit 0 input I 1 4 n Bit 1 0 fix n Bit 2 input I 1 5 n Bit 3 0 fix n Bit 4 input I 1 6 n Bit 5 0 fix n Bit 6 input I 1 7 n Bit 7 0 fix 12 15 00h fix 6 3 4 Technical data Order no 321 1BH70 Type SM 321S SPEED Bus SPEED Bus ü Current consumption power loss Current consumption from backplane bus 390 mA Power loss 5 W Technical data digital inputs Number of inputs 16 Cable length shielded ...

Page 101: ...ration 16 Input characteristic curve IEC 61131 2 type 1 Initial data size 2 Byte Status information alarms diagnostics Status display green LED per channel Interrupts yes Process alarm yes parameterizable Diagnostic interrupt yes parameterizable Diagnostic functions yes Diagnostics information read out possible Supply voltage display green LED Group error display none Channel error display none Is...

Page 102: ...ollects the binary control signals from the superordinate bus system and transmits them galvanically separated to the process level The module has to be provided with 24V via the front slot It has 16 channels and their status is moni tored via LEDs n 16 fast output channels isolated to SPEED Bus n Supply voltage DC 24V n Output voltage 0 5A n Useable for magnetic valve and DC contactor n Status mo...

Page 103: ...1 LEDs 2 flap with labeling strip 3 contact bar 4 flap opened with inner label Structure VIPA System 300S Digital Modules FAST SPEED Bus 322 1BH70 DO 16xDC 24V 0 5A HB140 SM DIO en Rev 16 43 103 ...

Page 104: ...ut is active the according LED is addressed F LED red Error when overload or short circuits 9 Output Q 0 7 10 Ground 1 11 Supply voltage DC 24V 2L 12 Output Q 1 0 19 Output Q 1 7 20 Ground 2 CAUTION Please regard that the voltage applied to an output channel must be the voltage supply applied to L Schematic diagram VIPA System 300S Digital Modules FAST SPEED Bus 322 1BH70 DO 16xDC 24V 0 5A HB140 S...

Page 105: ...ay of 1 to 0 6 12 µs Minimum load current Lamp load 5 W Parallel switching of outputs for redundant control of a load not possible Parallel switching of outputs for increased power not possible Actuation of digital input ü Switching frequency with resistive load max 100 kHz Switching frequency with inductive load max 0 5 Hz Switching frequency on lamp load max 10 Hz Internal limitation of inductiv...

Page 106: ...ronmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes 6 5 323 1BH70 DIO 16xDC 24V 0 5A The module has 16 channels that can be used either as inputs or outputs Every channel supports a diagnostic function i e as soon as an output is active the according input is set on 1 If there is a short circuit at the load the according input...

Page 107: ...t channel must be the voltage supply applied to L Due to the parallel connection of in and output channel per group a set output channel may be supplied via an applied input signal Thus a set output remains active even at power off of the voltage supply with the applied input signal Non observance may cause module demolition Structure VIPA System 300S Digital Modules FAST SPEED Bus 323 1BH70 DIO 1...

Page 108: ... I Q 0 7 10 Ground 1 11 Supply voltage DC 24V 2L 12 I Q 1 0 0 7 LED green per byte As soon as an input signal 1 or an active output is recognized the according LED is addressed 19 I Q 1 7 F LED red error at overload or short circuit 20 Ground 2 Schematic diagram VIPA System 300S Digital Modules FAST SPEED Bus 323 1BH70 DIO 16xDC 24V 0 5A HB140 SM DIO en Rev 16 43 108 ...

Page 109: ...DIO16 Alarm ETS in the hardware configuration it occupies 48byte of the input range of the CPU and 2byte in the output range and can be parame terized with 66byte of data The following parameters are at your disposal n Diagnostic interrupt global for all inputs n Edge selection switchable process interrupt per channel n Time stamp activation of a time stamp function per channel n Filter value for ...

Page 110: ... for an input the current time value is entered in the process image of the module at according edge Thus allows you to compare times of different input channels via your user application Via the parameter Time stamp you may activate the ETS system and define the edge of the input signal that initiates the process image entry of a time stamp You have the fol lowing options n No time stamp n Time s...

Page 111: ...s at a blurred input signal The entry happens as a factor of 2 56µs 2 56µs 40ms and is within the range 1 16000 The record set has the following structure Word 0 Input filter I 0 0 in 2 56µs steps 30 Input filter I 1 7 in 2 56µs steps The module occupies 48byte in the input address range and 2byte in the output address range of the CPU that have the following meaning Input address range Byte 0 40 ...

Page 112: ... 7 Status I 0 7 9 Edge lost n Bit 0 Status I 1 0 n n Bit 7 Status I 1 7 10 11 reserved The following bytes contain the values of the µs ticker for a channel at the time of an edge change Only the lower 16bit are taken over An overflow after 65ms has to be accordingly processed in the user application Byte 3 2 1 0 12 Time stamp I 0 1 Time stamp I 0 0 16 Time stamp I 0 3 Time stamp I 0 2 20 Time sta...

Page 113: ...last read access if more than one edge change took place the corresponding bit of edge lost FV is set Here the µs ticker entry contains the time of the last edge Example Byte 1 0 FA1 4 0 1 1 0 0 0 1 0 0 1 0 1 1 1 1 0 FV 8 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0 FA2 44 0 0 1 1 0 0 0 0 0 0 0 1 0 0 1 0 The consistent µs ticker entries can be determined by logical bit operations FA1 AND NOT FA2 Result bit ope...

Page 114: ...t process interrupt execution in OB 40 and branches in OB 82 to diagnostic interrupt processingincoming If during the diagnostic interrupt pro cessing other events are occurring at other channels that may also cause a process res diagnostic interrupt these are interim stored After the end of the diagnostic interrupt pro cessing at first all interim stored diagnostic interrupts are processed in the...

Page 115: ...rupt is not longer pos sible The record sets of the diagnostic range have the following structure Byte Bit 7 Bit 0 0 n set at module failure n Bit 1 0 fix n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set when external auxiliary supply is missing n Bit 7 5 0 fix 1 n Bit 3 0 Module class 1111b Digital n Channel information present n Bit 7 5 0 fix 2 00h fix 3 n Bit 5 0 0 fix n B...

Page 116: ...e 115 4 n Bit 6 0 channel type 70h Digital input n Bit 7 More channel types present n 0 no n 1 yes 5 Number of diagnostic bits the module puts out per channel here 08h 6 Number of channels of a module here 04h 7 n Bit 0 Error in channel group 0 I 0 0 I 0 3 n Bit 1 Error in channel group 1 I 0 4 I 0 7 n Bit 2 Error in channel group 2 I 1 0 I 1 3 n Bit 3 Error in channel group 3 I 1 4 I I 7 n Bit 7 ...

Page 117: ...nterrupt lost at n Bit 0 input I 1 4 n Bit 1 0 fix n Bit 2 input I 1 5 n Bit 3 0 fix n Bit 4 input I 1 6 n Bit 5 0 fix n Bit 6 input I 1 7 n Bit 7 0 fix 12 15 00h fix 6 5 4 Technical data Order no 323 1BH70 Type SM 323S SPEED Bus SPEED Bus ü Current consumption power loss Current consumption from backplane bus 390 mA Power loss 5 W Technical data digital inputs Number of inputs 16 Cable length shi...

Page 118: ...ngth shielded 1000 m Cable length unshielded 600 m Rated load voltage DC 24 V Reverse polarity protection of rated load voltage ü Current consumption from load voltage L without load 50 mA Output current at signal 1 rated value 0 5 A Output delay of 0 to 1 6 12 µs Output delay of 1 to 0 6 12 µs Minimum load current Lamp load 5 W Parallel switching of outputs for redundant control of a load not pos...

Page 119: ... SF LED Channel error display none Isolation Between channels ü Between channels of groups to 8 Between channels and backplane bus ü Insulation tested with DC 500 V Datasizes Input bytes 2 48 Output bytes 2 Parameter bytes 0 66 Diagnostic bytes 16 Housing Material PPE Mounting DIN rail SPEED Bus Mechanical data Dimensions WxHxD 40 mm x 125 mm x 120 mm Weight 200 g Environmental conditions Operatin...

Page 120: ...Order no 323 1BH70 UL certification yes KC certification VIPA System 300S Digital Modules FAST SPEED Bus 323 1BH70 DIO 16xDC 24V 0 5A Technical data HB140 SM DIO en Rev 16 43 120 ...