Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 87 of 131
Active Power Derating
Percentage
CtrMode
P3/3
100.0%
0
OvrFrqMax(Hz)
OvrFrqMin(Hz)
P2/3
OvrFrqSlop(P/s)
60.00
0.16%
61.50
60.40
OvrFrqRecoveryT(S)
RecovryFrq(Hz)
60
OvrFrqDeratingMode
0
Power vs Grid Frequency
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Power vs Grid Voltage
P1/3
Disable
VwCurveV2
106.00%
VwCurveV1
VwCurveP1
VwCurveP2
OPenLoopRespT(s)
100.00%
110.00%
0.0%
10.0%
Figure 6-11 Power Derating Parameters
Table 6-9 Active Power Derating Setup Ranges with Lower Limit, Default, and Upper Limit for IEEE 1547-2018 and CA Rule 21
SETTINGS RANGE
PARAMETER NAME
DESCRIPTION
IEEE1547
RULE 21
MIN DEFAULT MAX
MIN
DEFAULT MAX
VWCURVEV1 (%)
Grid
overvoltage
derating
starting
voltage V1
105.00
106.00
109.00
105.00
106.00
109.00
VWCURVEP1 (%)
Grid
overvoltage
derating
starting power
P1
0.00
100.00
100.00
0.00
100.00
100.00
VWCURVEV2 (%)
Grid
overvoltage
derating end
voltage V2
106.00
110.00
110.00
106.00
110.00
110.00
VWCURVEP2 (%)
Grid
overvoltage
0.0
0.0
100.0
0.0
0.0
100.0