Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 96 of 131
OTHER PARAMETERS
SETTING RANGE
PARAMETER
NAME
DESCRIPTION
IEEE 1547
RULE 21
MIN
DEFAULT
MAX
MIN
DEFAULT
MAX
OPERATIONOV
ERVOL
Operating
overvoltage
protection
value
100.00
120.00
135.00
100.00
120.00
135.00
VIRTUALDAMPING
The parameter
of Virtual
Damping
0.000
0.000
5.000
0.000
0.000
5.000
MPPT1_OPTV
OLLOWLIM(V)
OptiVoltMinMp
pt1
200.0
200.0
1500.0
200.0
200.0
1500.0
MPPT1_OPTV
OLUPLIM(V)
OptiVoltMaxM
p pt1
200.0
1000.0
1500.0
200.0
1000.0
1500.0
MPPT2_OPTV
OLLOWLIM(V)
OptiVoltMinMp
pt2
200.0
200.0
1500.0
200.0
200.0
1500.0
MPPT2_OPTV
OLUPLIM(V)
OptiVoltMaxM
p pt2
200.0
1000.0
1500.0
200.0
1000.0
1500.0
MPPT3_OPTV
OLLOWLIM(V)
OptiVoltMinMp
pt3
200.0
200.0
1500.0
200.0
200.0
1500.0
MPPT3_OPTV
OLUPLIM(V)
OptiVoltMaxM
p pt3
200.0
1000.0
1500.0
200.0
1000.0
1500.0
Power ON/OFF
Manual Power ON/OFF
Restarting the inverter is required after changing a parameter setting or manual (fault) shut-down. Press
ESC
or
ENT
to access the
M
AIN
M
ENU
. Scroll the curser down to highlight POWER ON/OFF and press
ENT
to select. Move
NOTICE!
Compatibility among the functions:
•
Only one of these four functions can be valid at one time: QU, PF(P), PF Setting and reactive power
setting.
•
LVRT will take priority over the following functions:
o
Anti-islanding, QU, PF(P), PF Setting, reactive power setting, active power setting, over
frequency derating, GFCI, Grid over frequency protection, Grid unbalance protection, DCI
protection.