Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 56 of 131
Figure 3-34 AC Output and Ground Cable Connection
Table 3-11 Torque and Conductor Specifications
CONNECTION POINT
CONDUCTOR RANGE
TORQUE VALUE
AC OUTPUT TERMINAL BLOCK
L1/L2/L3:
6 -3/0AWG(75/90
°C
Cu)
6 - 3/0AWG (90
°C
Al)
Neutral:
8 - 3/0AWG (75/90
°C
Cu/Al)
14.25 N-m (126 in-lbs
)
INTERNAL GROUNDING BAR
6-4 AWG (CU)
5.65 N-m
(
50 in-lbs
)
EXTERNAL GROUNDING POINT
6-4 AWG (CU)
5.65 N-m
(
50 in-lbs
)
The AC Terminals are 90°C rated. The maximum acceptable conductor size that may be terminated to the AC
output terminal is restricted based on the compression lug maximum dimensions shown in Figure 3-36.