Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 28 of 131
Figure 3-4 Inverter Wall Mounting Baffle Details
NOTICE!
Ensure that the air space around the inverter is well ventilated. The spacing between two adjacently wall
mounted inverters may be reduced to
≥
13.8in (350mm) provided a baffle is installed. Installing an aluminum
or galvanized steel baffle (Not supplied by Yaskawa Solectria Solar) with the dimensions detailed above is
intended to divert or deflect warm exhaust air from entering the adjacent inverter. Elevated ambient air
temperature
≥
45
°
C will cause the inverter to enter a thermal derating mode and reduce its active power
output.