background image

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480 

 

DOCR-071030-A (10/7/2022) 

 

Page 37 of 131 

 

 

Secure the Power Head to the Wiring Box 

Secure the wiring box to the main enclosure by using the M6x18 screws (4pcs) to fasten the wiring box (see Figure 

3-14 ).  

  

Tool required: No. 10 Wrench or No. 3 Phillips head screwdriver, torque value of 4 Nm (35.4in-lbs). 

      WARNING

 

Incorrect Torque Leads to Improper Bonding: 

Ensure the M6x18 screws (4 pcs) for Section 3.2.5.5 are properly 

torqued at 4 Nm (35.4 in-lbs). This connection provides an electrical grounding bond of the Wiring Box to the 

upper/main enclosures. 

 

 

Figure 3-14 Securing Wiring Box to Power Head 

 

Attach Enclosures to Mounting Bracket 

Attach the main enclosure and the Wiring Box to the mounting bracket with 

M6x18 screws

 (6 pcs) as shown in 

Figure 3-15. Tool required: No.3 Phillips head screwdriver, torque value of 4N.m (35.4in-lbs) 

  

Summary of Contents for Solectria PVI 25TL-208

Page 1: ...Commercial 1000VDC String Inverters Solectria PVI 25TL 208 Solectria PVI 50TL 480 Solectria PVI 60TL 480 Installation and Operation Guide Models PVI 25TL 208 PVI 50TL 480 PVI 60TL 480...

Page 2: ...ons 12 Smart Inverter Functions default state 12 Inverter Diagrams 13 Schematic Diagram and Circuit Design 15 Anti islanding Detection 17 DC Ground Fault Protection 17 Surge Suppression 17 DC Arc faul...

Page 3: ...Fault Shutdown and Troubleshooting 101 LED Status Panel Testing 101 LCD Fault and Troubleshooting 101 8 Maintenance and Decommissioning of Inverters 110 Product Maintenance 110 Uninstall the Inverter...

Page 4: ...0TL 480 DOCR 071030 A 10 7 2022 Page 4 of 131 IMPORTANT REGISTRATION AND WARRANTY INFORMATION For warranty to become active this inverter must be registered To activate warranty and register inverter...

Page 5: ...t be done only by qualified personnel Be sure to read this manual carefully before using the inverter Thank you for choosing a Yaskawa Solectria Solar grid tied PV inverter This PV inverter is a high...

Page 6: ...the instructions in this manual Failure to follow these instructions and other relevant safety procedures may result in voiding of the product warranty and or damage to the inverter or other property...

Page 7: ...Caution Risk of Electric Shock Timed Discharge Caution Hot Surface Do Not Touch Warning Hazardous voltage area under plastic cover Do not open fuse holders under load Proper PPE must be used while ac...

Page 8: ...product can expose you to chemicals including lead known to the State of California to cause cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca gov CAUTI...

Page 9: ...nts through the LCD interface and no fire smoke or voltage AC or DC to ground is present in the enclosure a Follow general safety practices including PPE to open the wiring box b Measure the DC curren...

Page 10: ...ipment a PV inverter and AC power distribution equipment The SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 inverters convert solar power DC to AC power suitable for use in buildings and back fe...

Page 11: ...rd optional allows for remote firmware upgrades and advanced controls of the inverter USER INTERFACE UI LCD screen with touchpad controls LONG SERVICE LIFE Designed with thin film capacitors to extend...

Page 12: ...ing KVA OVERHEAD kVA overhead to produce rated Active Power at 0 91 power factor LOAD REJECTION OVER VOLTAGE LROV PROTECTION Protection from LROV events NO NEUTRAL REQUIRED No neutral connection requi...

Page 13: ...3 of 131 Inverter Diagrams Figure 2 2 SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 Inverter Main Items of the Inverter Main inverter enclosure Inverter wiring box Inverter mounting bracket Coo...

Page 14: ...n 73mm 4 29in 109mm 0 32in 8mm 2 87in 73mm 4 29in 109mm Figure 2 4 Wire box Conduit Knockout Locations Knockouts for DC input 1 1 1 2 inch Trade Size Knockout for communication 4 3 4 inch Trade Size K...

Page 15: ...common DC bus The inverter uses line voltage and frequency measurements to synchronize to the grid and converts the available PV power to AC power by injecting balanced 3 phase AC current into the el...

Page 16: ...tdown system has been UL PVRSS listed and compatibility tested and is a certified platform to conform to 690 12 of the 2017 National Electric Code Please refer to the RSD Compatibility and Listing Mat...

Page 17: ...possible islanding condition If the grid is stable these small perturbations will have negligible effects on the system voltage frequency However in an islanded condition the changes in reactive power...

Page 18: ...ule and back Please refer to the RSD Compatibility and Listing Matrix Application Note for the most up to date information on models that have been tested and listed with Solectria inverters Every mod...

Page 19: ...unications Overview Labels The SOLECTRIA PVI 25TL 208 PVI 50TL 480 AND PVI 60TL 480 has labels on the Power Head Do not deface these labels as they contain important information required for warranty...

Page 20: ...O Do Not Discard Packaging Before Removing all Contents There are multiple components in each box Check packaging thoroughly before discarding 3 Installation This chapter describes the planning and in...

Page 21: ...block 5 M8 Flat washer 4 For AC terminal block 6 M8 Spring washer 4 For AC terminal block 7 Phillips screw 1 Spare for wiring box cover INFO The items above in Table 3 2 Accessory Kit are for the typ...

Page 22: ...rs Connected but Off Temperatures Max temp 70 C with no lower limit on temperature Inverter installed connected to electric utility grid but non operating daylight or nighttime hours The bulkhead conn...

Page 23: ...ss the PV array If the inverter is mounted outdoors without operating power for an extended period of time Yaskawa Solectria Solar recommends that the inverter power head be inspected for water conden...

Page 24: ...ind rain direct sun pests vegetation growth and any other local environmental conditions To increase its life span it is recommended that the inverter be installed out of direct sunlight for example u...

Page 25: ...from vertical If tilted at 15 from vertical 75 from horizontal or shallower closer to horizontal in an outdoor environment the Shade Cover accessory is required See Section 9 2 1 for more details Whe...

Page 26: ...the clearance area free from debris plants and other obstructions NOTICE Improper Installation Will Void Warranty The requirements defined in this section are the minimum allowable clearances In areas...

Page 27: ...PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 27 of 131 Figure 3 3 Inverter Minimum Spacing and Clearance Area NOTICE The installation clearance between two inverters must be increased to...

Page 28: ...cing between two adjacently wall mounted inverters may be reduced to 13 8in 350mm provided a baffle is installed Installing an aluminum or galvanized steel baffle Not supplied by Yaskawa Solectria Sol...

Page 29: ...80 DOCR 071030 A 10 7 2022 Page 29 of 131 Figure 3 5 Inverter Pillar or Column Mounting Dimensions INFO If the inverter is installed on a pillar or column instead of solid wall the space from the bott...

Page 30: ...Installation and Operation Guide SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 30 of 131 Figure 3 6 Inverter Pillar Mounting Specifications...

Page 31: ...OTICE Improper Installation Will Void Warranty Always use the provided mounting bracket secured to a structurally sound surface Never modify the inverter Power Head or Wiring Box enclosure Doing so wi...

Page 32: ...Installation and Operation Guide SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 32 of 131 Figure 3 7 Mounting Bracket Hole Locations...

Page 33: ...10mm 0 4in head 13mm wrench 240 in lbs INFO Mounting the Bracket to PV Racking the M8 nuts are not provided in the Accessory Kit Tools Required No 13 wrench es Concrete Wall Mount Drill holes at the m...

Page 34: ...t be used in order to avoid injuries The Power Head of the Solectria PVI 25TL 208 PVI 50TL 480 AND PVI 60TL 480 weighs 123 5 lbs 56kg Hang the inverter on the mounting bracket as shown in Figure 3 10...

Page 35: ...ue to the weight of the equipment Figure 3 11 Grab Handle Position Install the Wiring Box NOTICE It is not advisable to leave the Wiring Box Installed without the Power Head If it is absolutely necess...

Page 36: ...g box Figure 3 13 Wiring Bulkhead Cover INFO The covers shown above do not have waterproof function THEY ARE NOT WATER TIGHT Save the bulkhead connector cover and screws and attach the cover to the le...

Page 37: ...e value of 4 Nm 35 4in lbs WARNING Incorrect Torque Leads to Improper Bonding Ensure the M6x18 screws 4 pcs for Section 3 2 5 5 are properly torqued at 4 Nm 35 4 in lbs This connection provides an ele...

Page 38: ...r future use Tool required No 2 Phillips head screwdriver torque value of 1 6N m 14 2in lbs Figure 3 16 Attach Bulkhead Cover to Wiring Box Anti Theft Padlock Optional The Yaskawa Solectria Solar PVI...

Page 39: ...tor shall avoid touching live components with hazardous voltage and energy Verify the absence of voltage using an appropriately rated multimeter Always Wear Proper PPE The proper Personal Protective E...

Page 40: ...izing tool is available https solectria com support string sizing tool This is an optional design tool to help guide designers by matching the PV panel type and quantity to the inverter s power rating...

Page 41: ...the same location but no additional or new holes shall be created If the knockout holes are enlarged by the customer adequate room for water tight connections should be taken into consideration and a...

Page 42: ...in Figure 3 22 Figure 3 23 and Figure 3 24 Their different connection points are labeled as follows DC Input fuse holder terminal DC SPD Surge Protective Device Internal ground terminal AC output term...

Page 43: ...TL 208 Figure 3 25 shows the PVI 50TL 480 and PVI 60TL 480 standard wiring box with the fuse bypass option This option is used with external combiner boxes The three zones of these inverters must stay...

Page 44: ...ding the recommended DC to AC ratio may damage the inverter and will void the warranty Size strings according to information in this section and all applicable electrical codes DC AC Ratio and Current...

Page 45: ...s than 90 C 194 F All electrical conductors must meet the requirements of the NEC and local electrical codes Although these inverters operate with ungrounded PV arrays the PV system requires a DC equi...

Page 46: ...L Copper or Aluminum when using the Bypass Terminal kit accessory Terminals are 90 C rated 6 to 2 AWG INFO Even though the SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 3 Phase Inverters are de...

Page 47: ...r combined input strings for example when Y branch connectors are used with DC field wiring to reduce PV source circuit home runs Yaskawa Solectria Solar allows replacement of the factory installed 20...

Page 48: ...s is lower than 1000VDC under any conditions Confirm that the PV modules for each MPPT within the inverter are of the same type and specification before connection Ensure correct polarity of the PV St...

Page 49: ...ssembled using fuse holders supplied by either Sinofuse or Mersen Ferraz Shamut The touch safe fuse holders have unique terminal torque values specified by their manufacturers The fuse holders can be...

Page 50: ...the user manual i WARNING High touch current Earth connection essential before connecting supply AC OUTPUT Figure 3 29 DC Input connection Table 3 8 DC Electrical Installation DC Tools Required TOOL D...

Page 51: ...VI 60TL 480 wire boxes Fuse Bypass Terminals are available as an optional accessory when external PV string fused combiners are used The Bypass Terminals allow for larger single conductors to be termi...

Page 52: ...a floating WYE or floating delta service the inverter can only provide DC ground fault detection It is the customer s responsibility to provide AC ground fault detection external to the inverter to co...

Page 53: ...s recommended that the transformer VA rating be selected based on IEEE C57 159 2016 Guide on Transformers for application in Distributed Photovoltaic DPV Power Generation Systems It is the responsibil...

Page 54: ...Electric Shock Hazard Components with hazardous voltage and energy will electrocute operator Operator shall avoid touching live components with hazardous voltage and energy Verify the absence of volta...

Page 55: ...s can be made with the larger knockouts No new holes in unspecified areas are allowed or it will impact the NEMA 4X rating and wire box warranty DC INPUT COMM PORT For more details please see the user...

Page 56: ...ANGE TORQUE VALUE AC OUTPUT TERMINAL BLOCK L1 L2 L3 6 3 0AWG 75 90 C Cu 6 3 0AWG 90 C Al Neutral 8 3 0AWG 75 90 C Cu Al 14 25 N m 126 in lbs INTERNAL GROUNDING BAR 6 4 AWG CU 5 65 N m 50 in lbs EXTERN...

Page 57: ...potential The neutral conductor is for control or measurement purposes only and therefore may be sized according to NEC section 705 95 B The ground conductor PE is sized to section 250 122 Use the OT...

Page 58: ...disconnect the inverter from the grid should an overcurrent event occur Table 3 13 Selecting a breaker of another size may either result in nuisance tripping or rejection from the AHJ Table 3 12 Spec...

Page 59: ...ction is not made within 30 seconds of applying the grease repeat this process as an oxidized layer may have formed on top of the conductor This oxidized layer is a poorer conductor than the greased a...

Page 60: ...ne portal YConnect Pro that is used for remote diagnostics and automatic firmware upgrades Third party monitoring platforms are supported via RS 485 shielded twisted pair connection This section inclu...

Page 61: ...t is also used for allowing the connection of a third party monitoring system Connection to the Internet Connection to the Internet with the Ethernet Network Card is strongly recommended for SOLECTRIA...

Page 62: ...erter communication It is important to use shielded cable to ensure communication is not interrupted Separate Communication Conductors from Power Conductors Never run communication conductors in the s...

Page 63: ...ection If there are multiple inverters in the RS 485 network the selector switch S1 of the last inverter in the daisy chain should be in ON position to have the 120 terminal resistor enabled The selec...

Page 64: ...e wiring box 7 Reconnect the AC and DC power and turn the inverter on when it is safe 8 Configure the Inverter Modbus ID and Baud rate 4 User Interface This section is intended to orient the user with...

Page 65: ...g but derated light on 0 5s light off 1 6s Off In other operation status or power supply not working GRID Grid Status Indicator Light On Grid normal Flash Grid fault on 0 5 seconds off 1 6 seconds Off...

Page 66: ...ng to the indications of the LCD The LCD screen will display different interfaces based on the operation modes of the inverter There are four operation modes Logo Start up interface Normal operation S...

Page 67: ...ce While the inverter is in Normal Operation mode and not in screen saver the interface indicates PV voltage PV current grid voltage instant power daily generated power and time This is the Default In...

Page 68: ...any hazards that may be present Commissioning Checklist WARNING Follow the Checklist For your safety please follow the guidelines below during the startup of your inverters Mechanical Installation En...

Page 69: ...y potential Use proper safety equipment when energizing the inverter Follow these instructions when turning on an inverter Turn ON the site AC breaker for the inverter Complete the connection of the i...

Page 70: ...ress ENT Scroll up down to select the numerical value then press ENT to go to next option e g Year to Month press ESC to go to last option e g Month to Year Finally Press the ENT key to confirm the se...

Page 71: ...inverter within the Modbus network must have a unique address Unit ID Scroll up down to choose an address for the inverter and press ENT Addresses can be assigned from 1 128 See Figure 5 4 Communicati...

Page 72: ...orded This information will show on the LCD screen as shown in the Figure 5 6 Current Error P1 1 Date Fault 2015 10 22 12 20 08 ArcboardErr 2015 10 22 12 20 08 2015 10 22 12 20 08 Fault0040 2015 10 22...

Page 73: ...in screen you should press ENT to select the operation information as shown in Figure 6 2 Check the information by pressing UP and DOWN Return to the previous menu by pressing ESC Figure 6 2 MEASUREME...

Page 74: ...ere are 8 submenus in Parameters Setting SYSTEM PARAMETERS CONTROL COMMAND PROTECTION PARAMETERS L HVRT PARAMETERS ACTIVE DERATING SETTING REACTIVE DERATING SETTING ARC PARAMETERS and OTHER PARAMETERS...

Page 75: ...Select Yes or No if a neutral conductor has been connected to the inverter This setting does not affect the operation of the inverter When a neutral is installed and Yes is selected the inverter will...

Page 76: ...s the arcing protection signal to the DSP in the control board The control board DSP is responsible for disconnecting the inverter from the grid after receiving the arcing signal to ensure safety The...

Page 77: ...an t enable disable the function The protect parameters are shown in Table 6 1 Figure 6 7 Protection Parameters Setting INFO There are 7 pages of parameters displayed Switching between parameters is d...

Page 78: ...DVOLTMAX3 Level 3 Max grid voltage 100 00 120 00 135 00 100 00 120 00 135 00 VOLTMAXTRIPTIME3 S Level 3 Max grid trip voltage 0 00 0 16 655 00 0 00 0 16 655 00 GRIDVOLTMIN1 Level 1 Min Grid voltage 30...

Page 79: ...RQMAX3 HZ Protection threshold value of Level 3 Max grid frequency 60 00 62 00 65 00 60 00 62 00 65 00 FRQMAXTRIPT3 S Trip time of Level 3 Max grid frequency 0 00 0 16 655 00 0 00 0 16 655 00 GRIDFRQM...

Page 80: ...90 00 100 00 VOLRECOVERYT S Recovery time of grid voltage protection 0 00 300 00 655 00 0 00 300 00 655 00 FRQMAX HZ Recovery Max threshold grid Frequency protection 54 00 60 30 66 00 54 00 60 40 66...

Page 81: ...00 600 00 655 00 0 00 600 00 655 00 Table 6 5 Grid Voltage Balance Grid Voltage Balance Setting Range IEEE1547 RULE21 PARAMETER NAME DESCRIPTION MIN DEFAULT MAX MIN DEFAULT MAX GRIDVOLBALANCE Unbalan...

Page 82: ...VRTTime8 s LVRTVol7 LVRTVol8 HVRTTime1 s HVRTVol1 P4 7 0 80 125 00 0 00 125 00 HVRTVol2 124 00 0 80 P5 7 12 50 115 00 12 50 124 00 115 00 12 50 HVRTTime2 s HVRTTime3 s HVRTVol3 HVRTVol4 HVRTTime4 s HV...

Page 83: ...IPTION MIN DEFAULT MAX MIN DEFAULT MAX LVRTVOLT 1 2 Threshold value of Low voltage ride through 1st 2nd point 0 00 0 00 0 00 0 00 100 00 100 00 0 00 0 00 0 00 0 00 100 00 100 00 LVRTTIME 1 2 S Time of...

Page 84: ...00 65 00 100 00 100 00 LVRTTIME 5 6 S Time of Level Low voltage ride through 5th 6th point 0 00 0 00 10 50 20 50 655 00 655 00 0 00 0 00 10 50 20 50 655 00 655 00 LVRTVOLT 7 8 Threshold value of Low v...

Page 85: ...urth point 100 00 100 00 124 00 124 00 135 00 135 00 100 00 100 00 120 00 120 00 135 00 135 00 HVRTTIME 3 4 S Time of Level high voltage ride through third or fourth point 0 00 0 00 0 80 12 50 655 00...

Page 86: ...0 100 0 LVRTPSTREACTIVE The coefficient of positive sequence reactive current 0 150 0 300 0 0 0 150 0 300 0 LVRTNEGREACTIVE The coefficient of negative sequence reactive current 0 200 0 300 0 0 0 200...

Page 87: ...Voltage P1 3 Disable VwCurveV2 106 00 VwCurveV1 VwCurveP1 VwCurveP2 OPenLoopRespT s 100 00 110 00 0 0 10 0 Figure 6 11 Power Derating Parameters Table 6 9 Active Power Derating Setup Ranges with Lower...

Page 88: ...60 00 61 40 72 00 60 00 62 00 72 00 OVRFRQSLOP HZ The Rate of Overfrequency derating 0 01 0 16 100 00 0 01 30 00 100 00 RECOVERYFRQ HZ The recovery frequency of OverFrequency derating 58 80 60 00 66 0...

Page 89: ...meters Protection Parameters Power Derating Setup Reactive Power Derating Setup ARC Parameters Control Command PFSetValue 1 000 ReactivePowerOver Disable Figure 6 12 ReactivePowerDerating Parameter Sc...

Page 90: ...AX PFPCURVEP1 Power of PF P Curve point 1 0 0 50 0 110 0 0 0 50 0 110 0 PF_PCURVEPF1 PF of PF P Curve point 1 1 000 0 800 1 000 0 800 1 000 1 000 0 800 1 000 0 800 1 000 PFPCURVEP2 Power of PF P Curve...

Page 91: ...ive compensation changes according to the grid voltage as shown in Figure 6 15 Figure 6 15 Q U Curve Mode Curve INFO PF P Curve and Q U Curve Functions These functions are only available for IEEE 1547...

Page 92: ...Curve point 1i 90 00 92 01 100 00 90 00 96 70 100 00 QUCURVEQ1I Reactive power of Q U Curve point 1i 66 0 0 0 66 0 66 0 0 0 66 0 QUCURVEU2I V Voltage of Q U Curve point 2i 80 00 90 00 92 00 80 00 92...

Page 93: ...are only to be changed by Yaskawa Solectria Solar personnel with approval from the AHJ LVRT HVRT Setup Setting P1 2 System Parameters Protection Parameters Power Derating Setup Reactive Power Deratin...

Page 94: ...rVol 120 00 Enable VirtualDamping 0 Others P6 7 MPPT1_OptVo1LowLim Others P7 7 Anti reflux DSP MPPT1_OptVo1UpLim MPPT2_OptVo1LowLim MPPT2_OptVo1UpLim MPPT3_OptVo1LowLim MPPT3_OptVo1UpLim 200 0 1000 0...

Page 95: ...m DCI value1 0 1 0 5 5 0 0 1 0 5 5 0 DCIPROTECTIONT1 S Trip time 1 of DCI value 0 00 60 00 120 00 0 00 60 00 120 00 DCIPROTECTION2 mA maximum DCI value2 5 950 5000 5 950 5000 DCIPROTECTIONT2 S Trip ti...

Page 96: ...PTV OLUPLIM V OptiVoltMaxM p pt2 200 0 1000 0 1500 0 200 0 1000 0 1500 0 MPPT3_OPTV OLLOWLIM V OptiVoltMinMp pt3 200 0 200 0 1500 0 200 0 200 0 1500 0 MPPT3_OPTV OLUPLIM V OptiVoltMaxM p pt3 200 0 100...

Page 97: ...set value the AC power grid fails or the ambient temperature exceeds the normal range History Record Move the cursor to HISTORY RECORD in the MAIN MENU interface Press ENT to check the historical rec...

Page 98: ...evice Information Setting PmaxLim SmaxLim HMI 01 06 0 0100 HMI Boot 01 00 MiniMCU 99 99 CPLD 15 00 Reserve Figure 6 19 Device Information This menu provides the information to identify the version of...

Page 99: ...at the maximum power point In case of any grid abnormality the inverter will enter the protection program immediately In low light conditions when PV power generation is not sufficient to keep the inv...

Page 100: ...P and follow the prompts on the screen See Figure 6 21 5 When the update is successful repeat the process if necessary to update the next firmware DSP or LCD Should the update fail return to step 4 wh...

Page 101: ...STATUS SOLUTIONS NEITHER THE POWER LED NOR THE LCD SCREEN LIGHTS UP 1 Turn off the external AC breaker 2 Switch the DC switch to OFF position 3 Check the PV input voltage and polarity THE GRID LED IS...

Page 102: ...ircuit could be hazardous and the following procedures should be followed before turning OFF the DC Switch under fault conditions WARNING All the installation and wiring connections should be performe...

Page 103: ...ternal AC disconnect then back on to reboot the system 6 Contact the technical support team EXTFANERR Definition Cooling fan failure Possible causes 1 Fan is blocked 2 Fan service life has expired 3 F...

Page 104: ...echnical support team WARN0050 TEMPSENSORER R Recommended solutions 1 Observe temperature display 2 Switch off external AC disconnect then back on to reboot the system 3 Contact the technical support...

Page 105: ...ange 2 Check the measured frequency value on the LCD if the grid frequency is within limit restart the inverter PROTECT0020 GRID RELAY ERROR Recommended solutions 1 Restart inverter by turning both AC...

Page 106: ...ate PV strings Test strings with multimeter or equivalent 3 Add one PV string at a time and start up inverter to see if alarm occurs 4 If there is no alarm turn OFF AC switches to disconnect from the...

Page 107: ...er cannot clear fault replace inverter PROTECT0100 LEAKAGE CURRENT SENSOR FAULT Recommended solutions 1 Restart inverter by turning both AC and DC switches OFF Wait for 1 minute for all energy to disc...

Page 108: ...OFF Wait for 1 minute for all energy to discharge and turn both switches ON 2 If inverter cannot clear fault replace inverter ARC PROTECT Recommended solutions 1 Check if the logic connector is secur...

Page 109: ...itch to disconnect inverter from grid 2 Open fuse holders to isolate PV strings Test strings with meter 3 Add one PV string and start inverter to see if alarm occurs 4 If no alarm turn OFF AC switches...

Page 110: ...1 Overcurrent or PV2 Overcurrent or PV3Overcurrent 8 Maintenance and Decommissioning of Inverters This section defines the activities required to properly maintain the inverter and must be done by qua...

Page 111: ...t may be necessary to replace the external fans Please refer to Figure 8 1 for replacing the cooling fans Use a No 2 Phillips head screwdriver to remove the 10 screws on the fan tray 6 screws on the u...

Page 112: ...s in order to avoid inverter failure or possible electrical shock that could result in death Replace the Inverter Please confirm the following items before replacing the inverter The AC breaker of inv...

Page 113: ...ng box Lift the inverter enclosure and disconnect from the wiring box Figure 8 5 Disconnect the Main Housing from the Wiring Box If the replacement inverter is to be installed immediately skip this st...

Page 114: ...disconnect switch if present and use lock out tag out procedures Skip this step if there is no DC circuit breaker Switch the inverter s AC disconnect switch to OFF position Switch the inverter s DC di...

Page 115: ...nd IN3 are isolated from one another by design although the MPPT negative inputs IN1 IN2 and IN3 are combined via a common bus structure The Fuse Bypass Terminals MTLSR 070553 for all 3 models Bypass...

Page 116: ...8 PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 116 of 131 Figure 9 1 Remove Wirebox Cover Figure 9 2 Remove Plastic Touchsafe Finger Guards Figure 9 3 Bypass Terminals Installed on POS I...

Page 117: ...ion from Harsh Conditions Shade covers provide added protection for inverters against harsh environmental conditions like direct sunlight snow sleet ice hail and reduce soiling from dust and birds If...

Page 118: ...to 15 reduction in operating temperatures of inverters with shade covers installed in direct sunlight Shade Cover Installation Figure 9 7 Shade Cover Installation Steps 1 and 2 NOTICE Inverters at 75...

Page 119: ...L 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 119 of 131 Figure 9 8 Shade Cover Installation Steps 3 and 5 Install top bracket as shown Nuts M10 2 pcs Torque to 50 in lbs 5 6 N m Install bottom...

Page 120: ...MPPT 204A 68A per MPPT NUMBER OF DC INPUTS 6 inputs 2 per MPPT 15 inputs 5 per MPPT DC DISCONNECTION TYPE Load rated DC switch DC SURGE PROTECTION Type II MOV 1240VC 15kA ITM 8 20 S AC OUTPUT RATED AC...

Page 121: ...et Network Card 1 per 32 inverters MODBUS DATA MAPPING Solectria Proprietary Complies with SunSpec Modbus REMOTE DIAGNOSTICS FW UPGRADE FUNCTIONS Standard with Ethernet Network Card MECHANICAL DATA DI...

Page 122: ...ot a measuring instrument and has wider tolerances for the measurements it makes Inverter tolerances are generally 5 for real time measurements with output power below 20 nominal power 3 for real time...

Page 123: ...ability to operate from 200 950 Vdc Operating Voltage Range it will only be able to output full rated power for its model from a limited Maximum Power Voltage Range for each model see graphs For exam...

Page 124: ...lation and Operation Guide SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 124 of 131 Figure 10 2 PVI 50TL 480 Derating with respect to DC Voltage PVI 50TL 480 PVI 50...

Page 125: ...OCR 071030 A 10 7 2022 Page 125 of 131 Figure 10 3 PVI 60TL 480 Derating with respect to DC Voltage High Temperature Derating Graph When the ambient temperature is higher than 113 F 45 C the inverter...

Page 126: ...Guide SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 126 of 131 Pin Pn Tamb 45 60 100 80 60 40 20 3 Figure 10 4 PVI 25TL 208 PVI 50TL 480 AND PVI 60TL 480 Derating C...

Page 127: ...2022 Page 127 of 131 Altitude Derating Graph When the altitude is higher than 9842 5ft 3000m the rated output power Pn of the inverter will decrease as shown in Figure 10 5 Pin Pn 3000 4000 Altitude...

Page 128: ...d Output Voltage the inverter output power Pn may reach 100 When the grid voltage is lower than the Rated Output Voltage the inverter will limit the AC Output Current and the output power Pn will begi...

Page 129: ...Pn will begin to derate shown in Figure 10 3 2 20 40 60 80 100 Po Pn 0 88 Un Un 1 06 Un 1 1 Un Grid Voltage Vac volt watt function enable Figure 10 7 PVI 25TL 208 PVI 50TL 480 AND PVI 60TL 480 Derati...

Page 130: ...Installation and Operation Guide SOLECTRIA PVI 25TL 208 PVI 50TL 480 and PVI 60TL 480 DOCR 071030 A 10 7 2022 Page 130 of 131 Figure 10 8 Reactive Power Capability...

Page 131: ...ion please visit http solectria com support documentation warranty information grid tied inverter warranty letter Datasheet For the most up to date official datasheet please visit www solectria com Co...

Reviews: