Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 70 of 131
c.
The default grid standard is IEEE 1547. If a different standard is needed please go to “Menu
Functions” section for further instructions on how to change it. Available grid standards are shown in
INFO
✔
Please check with your local electricity provider before selecting the grid standard. If the inverter is operated
with a wrong grid standard, the electricity provider may cancel the interconnection agreement. Putting the
inverter into operation before the overall system complies with the national rules and safety regulation of the
application is not permitted.
Figure 5-2- Select Grid Standard; ML-Molokai/Lanai; OHM- O`ahu, Maui, and Hawai`i
Setting the Time. From the previous menu, press
ESC
to return to the System Parameters menu. Select
Time and press
ENT
. Scroll up/down to select the numerical value, then press
ENT
to go to next option.
e.g.: Year to Month, press
ESC
to go to last option. e.g.: Month to Year. Finally Press the
ENT
key to
confirm the setting. (Press the “up” arrow more than 1 second to go to last position of the number when
setting the parameters. e.g: 20
0
8 to 200
8
. Press the “down” arrow more than 1 second to go to the next
position of the number when setting the parameters. e.g:
2
008 to 2
0
08.)
The factory default working mode of the DC input connection and MPP Tracker is set for Independent and
shall only be configured as Independent. Parallel is not an option for this inverter line.
Neutral Line Setting. From the previous menu, press ESC to return to the System Parameters menu.
Select Neutral Line Setting and press ENT. Use the arrow keys to highlight “Yes” or “No” in regard to
whether a neutral conductor is present. Press ENT. This setting will allow the inverter to display L-N
voltages on the LCD. It will not affect the operation of the inverter.
Grid Connection Rule
CA Rule-21/UL 1741 SA
HECO-ML
HECO-HM
IEEE1547
NONE