SIEP C730600 92A YASKAWA AC Drive Option SI-EN3 Technical Manual
9 Input Assemblies (Drive Produces)
9
Input Assemblies (Drive Produces)
Note:
The convention in this manual is from the PLC perspective. An “Input Assembly” is outputted from this node and read by the
PLC. This section details “Input Assemblies” that are “Produced” by this drive.
Basic Speed Control Input - 70 (0x46)
Extended Speed Control Input - 71 (0x47)
Input
Instance Word Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
0
0
–
–
–
–
–
Running 1
(FWD)
–
Faulted
1
–
1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Parameter
Data
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2
SS
(SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 2
2
= 4096 = 0x1000
Unit depends on o1-03.
Input
Instance Word Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
71
0
0
At Speed
Ref from Net Ctrl from Net
Ready
Running 2
(REV)
Running 1
(FWD)
Warning
Faulted
1
Drive State
1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Warning
Warning
0: No Warning Occurred
1: Warning Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Running 2 (REV)
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Ready
Drive Ready
0: Not Ready
1: Ready
Ctrl from Net
Status of Run command from Network
0: Run command is not from network
1: Run command is from network