6 Related Drive Parameters
YASKAWA ELECTRIC
SIEP C730600 92A YASKAWA AC Drive Option SI-EN3 Technical Manual
25
Table 7 Option Monitors
F7-20
(3F8)
EtherNet/IP Power Scaling Factor
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0
Min.: -15
Max.: 15
F7-21
(3F9)
EtherNet/IP Voltage Scaling Factor
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID
2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
(3FA)
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0
Min.: -15
Max.: 15
F7-23 to
F7-32
(3FB to
404)
Dynamic Output Assembly
Parameters
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly
116 will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus
register.
Default: 0
F7-33 to
F7-42
(405 to
40E)
Dynamic Input Assembly
Parameters
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will
be read from this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value sent for
Input Assembly 166 is not defined by the user, therefore the option default
register value will be returned.
Refer to Input Assemblies (Drive Produces) on page 36
for definitions of
the default MEMOBUS/Modbus registers.
Default: 0
<1> Set b1-02 = 3 to start and stop the drive with the EtherNet/IP master device using serial communications.
Set b1-01 = 3 to control the frequency reference of the drive via the master device.
<2> Setting this parameter to 3 will cause the drive to continue operation after detecting a fault. Take proper measures such as installing an
emergency stop switch when using setting 3.
<3> Settings 4 and 5 are not available on 1000-Series drives.
<4> Control method availability of this parameter depends on drive series.
1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.
In AOLV/PM, this value is read as the Torque Limit.
GA700 Drives: Parameter is available in CLV, AOLV, AOLV/PM, and CLV/PM.
<5> The setting specifies that network communications provide the torque reference or torque limit. The motor could rotate if the PLC does not
supply a torque reference or torque limit.
<6> Cycle power for setting changes to take effect.
<7> Set F7-01 to F7-04 when F7-13 is set to 0. All IP Addresses (F7-01 to F7-04) must be unique.
<8> Set F7-01 to F7-12 when F7-13 is set to 0.
<9> Set F7-15 when F7-14 is set to 0 or 2.
No.
Name
Description
Range
U6-80 to U6-83
OPT IP ADR 1 to 4
Displays IP Address currently available;
• U6 -80: First octet
• U6 -81: Second octet
• U6 -82: Third octet
• U6 -83: Forth octet
0 to 255
U6-84 to U6-87
Online Subnet 1 to 4
Displays subnet currently available;
• U6 -84: First octet
• U6 -85: Second octet
• U6 -86: Third octet
• U6 -87: Forth octet
0 to 255
U6-88 to U6-91
Online Gateway
Displays gateway currently available;
• U6 -88: First octet
• U6 -89: Second octet
• U6 -90: Third octet
• U6 -91: Forth octet
0 to 255
U6-92
Online Speed
Displays CN1 Port 1 link speed currently available.
10: 10 Mbps
100: 100 Mbps
U6-93
Online Duplex
Displays CN1 Port 1 duplex setting currently available.
0: Half, 1: Full
U6-98
First Fault
Displays first option fault. Refer to
for details.
–
U6-99
Current Fault
Displays current option fault. Refer to
for details.
–
No.
(Addr.
Hex)
Name
Description
Values
EtherNet_conditional_E.book 25 ページ 2016年6月28日 火曜日 午後11時30分