5 Installation Procedure
YASKAWA ELECTRIC
SIEP C730600 92A YASKAWA AC Drive Option SI-EN3 Technical Manual
21
4.
Insert the option card (B) into the CN5-A connector (I) on the drive and fasten it into place using the included
screws (C). Tighten both screws to 0.5 to 0.6 N
m (4.4 to 5.3 in. lbs).
Note:
Installing the option card on a GA700 drive requires only two screws and does not require a ground wire. The option package
ships with three screws and a ground wire for installation on other drive series. Do not use the ground wire or the extra screw.
Figure 20
Figure 20 Insert the Option Card
5.
Firmly connect the Ethernet communication cable to the option modular connector (CN1).
Install Ethernet communications cables apart from main-circuit wiring and other electrical and power lines.
Ensure the cable end is firmly connected (see
).Refer to
Communication Cable Specifications on
for details.
Note: 1.
Separate communication cables from main circuit wiring and other electrical lines.
2.
Maximum transmission distance is 100 m (328 ft.). Minimum wiring distance between stations is 0.2 m (7.9 in).
6.
Replace and secure the LED Status Ring board (H).
Use the open space provided inside the LED Status Ring board to route option wiring.
NOTICE:
Do not pinch cables between the front cover or the LED Status Ring board and the drive. Failure to comply could cause
erroneous operation.
7.
Replace and secure the front cover of the drive (D) including the keypad (F).
Figure 21
Figure 21 Replace the Front Cover and Keypad
8.
Set drive parameters in
for proper option performance.
I
C
B
A1000
H
D
F
Install the keypad to the drive after replacing
the keypad connector and then the keypad
connector. At that time, insert the keypad
connector tab into the drive.
Keypad
connector
Tab
A1000
EtherNet_conditional_E.book 21 ページ 2016年6月28日 火曜日 午後11時30分