40
YASKAWA
TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
◆
Analog Value Objects
Table 7.3 Analog Value Objects
Object
ID
Object Name
(
Network Display
)
Modbus
Address
(Hex.)
Precision
Range
Units
PV
Access
AV1
Operation Cmd (Bitmapped)
(
Operation Cmd
)
•
bit 0: Run Fwd
•
bit 1: Run Rev
•
bit 2: External Fault (EF0)
•
bit 3: Fault Reset
•
bit 4: Multi-Function Input 1
(ComRef when
H1-01 = 40
)
•
bit 5: Multi-Function Input 2
(ComCtrl when
H1-02 = 41
)
•
bit 6: Multi-Function Input 3
•
bit 7: Multi-Function Input 4
•
bit 8: Multi-Function Input 5
•
bit 9: Multi-Function Input 6
•
bit A: Multi-Function Input 7
•
bit B to F: Reserved
Note:
When you use AV1, you
must not use BV1 to BV11
or AV5.
0001
-
0 - 2047
Bitmap
ped
C
AV2
Frequency Command
(
Frequency Cmd
)
0002
xxx . xx
Determined by o1-03
0.00 -
600.00
Deter
mined by
o1-03
C
AV3
PID Setpoint
(
PI Setpoint Cmd
)
0006
xxx . xx
0.00 -
100.00
%
C
AV4
MF Output Cmd (Bitmapped)
(
MF Output Cmd
)
•
bit 0: Multi-Function Digital
Output 1 (terminal M1-M2)
•
bit 1: Multi-Function Digital
Output 2 (terminal M3-M4)
•
bit 2: Multi-Function Digital
Output 3 (terminal M5-M6)
•
bit 3: Reserved
•
bit 4: Reserved
•
bit 5: Reserved
•
bit 6: Enables the function in
bit 7
0009
-
0 - 257
Bitmap
ped
C