50
YASKAWA
TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
Object ID
Object Name
(
Network Display
)
Modbus
Address
(Hex.)
Active Text
Inactive Text
PV Access
BV38
Frequency Detect 2
(
Frequency Detect 2
)
002C: bit 5
ON
OFF
R
BV39
Drive Startup Complete
(
Drv Startup Complete
)
002C: bit 6
ON
OFF
R
BV40
Low Voltage Detect
(
Low Voltage Detect
)
002C: bit 7
ON
OFF
R
BV41
Base Block
(
Base Block
)
002C: bit 8
ON
OFF
R
BV42
Frequency Reference
Mode
(
Frequency Ref Mode
)
002C: bit 9
LOCAL
COM
R
BV43
Run Command Mode
(
Run Command Mode
)
002C: bit 10
LOCAL
COM
R
BV44
Overtorque Detect
(
Over Torque Detect
)
002C: bit 11
ON
OFF
R
BV45
Frequency Refer Lost
(
Frequency Ref Loss
)
002C: bit 12
ON
OFF
R
BV46
Retry Error
(
Retry Error
)
002C: bit 13
ON
OFF
R
BV47
Modbus Comms Error
(
Modbus Comms Error
)
002C: bit 14
ON
OFF
R
BV48
Modbus Timeout Error
(
Modbus Timeout Error
)
002C: bit 15
ON
OFF
R
BV49
CRC Error
(
CRC Error
)
003D: bit 0
ON
OFF
R
BV50
Invalid Data Length
(
Invalid Data Length
)
003D: bit 1
ON
OFF
R
BV51
Parity Error
(
Parity Error
)
003D: bit 3
ON
OFF
R
BV52
Overrun Error
(
Overrun Error
)
003D: bit 4
ON
OFF
R
BV53
Framing Error
(
Framing Error
)
003D: bit 5
ON
OFF
R