TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
Object ID
Object Name
(
Network Display
)
Modbus
Address
(Hex.)
Active Text
Inactive Text
PV Access
BV6
COM CNTRL
(
Com Cntrl Cmd
)
Internal
COM
LOCAL
C
BV7
MF Input 3 Cmd
(
MF Input 3 Cmd
)
0001: bit 6
ON
OFF
C
BV8
MF Input 4 Cmd
(
MF Input 4 Cmd
)
0001: bit 7
ON
OFF
C
BV9
MF Input 5 Cmd
(
MF Input 5 Cmd
)
0001: bit 8
ON
OFF
C
BV10
MF Input 6 Cmd
(
MF Input 6 Cmd
)
0001: bit 9
ON
OFF
C
BV11
MF Input 7 Cmd
(
MF Input 7 Cmd
)
0001: bit 10
ON
OFF
C
BV12
Set Fault Contact Cmd
(
Set Flt Contact Cmd
)
0009: bit 6
ENABLE
OFF
C
BV13
RUN-STOP
(
RUN-STOP
)
0020: bit 0
RUN
OFF
R
BV14
REV-FWD
(
REV-FWD
)
0020: bit 1
REV
FWD
R
BV15
READY
(
READY
)
0020: bit 2
READY
OFF
R
BV16
FAULT
(
FAULT
)
0020: bit 3
FAULTED
OFF
R
BV17
Data Set Error
(
Data Set Error
)
0020: bit 4
ERROR
OFF
R
BV18
Overcurrent - Ground
Fault
(
OverCurrent- Gnd Flt
)
0021: bit 0
OC-GF
OFF
R
BV19
Main Circuit Overvoltage
(
Main Ckt OverVoltage
)
0021: bit 1
OV
OFF
R
BV20
Drive Overload
(
Drive OverLoad
)
0021: bit 2
OL2
OFF
R
BV21
Drive Overheat
(
Drive OverHeat
)
0021: bit 3
OH1-OH2
OFF
R