YASKAWA
TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
55
Code
Name
Causes
Possible Solutions
oFA01
Option Card Fault
(CN5-A)
The option connected to option
port CN5-A was changed during
run.
1.
De-energize the drive.
2.
Connect the option to the correct
option port.
oFA03,
oFA04
Option Card Error
(CN5-A)
A fault occurred in the option.
1.
De-energize the drive.
2.
Make sure that the option is
correctly connected to the connector.
3.
If the problem continues, replace the
option.
oFA30 to
oFA43
Option Card
Connection Error
(CN5-A)
A fault occurred in the option.
1.
De-energize the drive.
2.
Make sure that the option is
correctly connected to the connector.
3.
If the problem continues, replace the
option.
oFb00
Option Not
Compatible with Port
The option connected to
connector CN5-B is not
compatible.
Connect the option to the correct
connector.
•
Use connector CN5-A when you
connect the option.
To use other options, refer to those
option manuals.
oFb02
Option Fault
An option of the same type is
already installed in option port
CN5-A, CN5-B, or CN5-C.
Connect the option to the correct option
port.
oFC00
Option Not
Compatible with Port
or Option Fault (CN5-
C)
The option connected to
connector CN5-C is not
compatible.
Connect the option to the correct
connector.
•
Use connector CN5-A when you
connect the option.
To use other options, refer to those
option manuals.
oFC02
Option Fault
An option of the same type is
already installed in option port
CN5-A, CN5-B, or CN5-C.
Connect the option to the correct option
port.
■
Minor Faults and Alarms
Code
Name
Causes
Possible Solutions
CyPo
Cycle Power to
Active Parameters
Comm. Option Parameter Not
Upgraded
Re-energize the drive to update the
communication option parameters.
◆
Option Compatibility
You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
•