YASKAWA
TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
43
Object
ID
Object Name
(
Network Display
)
Modbus
Address
(Hex.)
Precision
Range
Units
PV
Access
AV10
Output Frequency
(
Output Frequency
)
0041
xxx . xx
Determined by o1-03
-
Deter
mined by
o1-03
R
AV11
Output Voltage
(
Output Voltage
)
0045
xxxx . x
-
V
R
AV12
Output Current
(
Output Current
)
0026
xxxx . x (for drives
rated higher than 11
kVA)
xxx . xx (for drives
rated 11 kVA or
lower)
-
A
R
AV13
Output Power
(
Output Power
)
0047
xxxx . x (for drives
rated higher than 11
kVA)
xxx . xx (for drives
rated 11 kVA or
lower)
-
kW
R
AV14
Torque Reference
(
Torque Reference
)
0048
xxxx . x
-
%
R
AV15
MF Input Status
(
MF Input Status
)
002B
-
0 - 127
Bitmap
ped
R
AV16
Drive Status 2
(
Drive Status 2
)
002C
-
1 - 65535
Bitmap
ped
R
AV17
MF Output Status
(
MF Output Status
)
002D
-
0 - 135
Bitmap
ped
R
AV18
DC Bus Voltage
(
DC Bus Voltage
)
0031
xxxx . x
-
V
R
AV19
PID Feedback Level
(
PI Feedback Level
)
0038
xxxx . x
-
%
R
AV20
PID Input Level
(
PI Input Level
)
0039
xxxx . x
-
%
R
AV21
PID Output Level
(
PI Output Level
)
003A
xxxx . x
-
%
R
AV22
CPU Software
(
CPU Software
)
004D
xxxxx
-
-
R
AV23
Flash Number
(
Flash Number
)
005B
xxxxx
-
-
R