38
YASKAWA
TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
Property
Object Type
Device
Analog
Input
(AI)
Analog
Output
(AO)
Analog
Value
(AV)
Binary
Input
(BI)
Binary
Output
(BO)
Binary
Value
(BV)
Status_Flags
-
Yes
Yes
Yes
Yes
Yes
Yes
Event_State
-
-
-
-
-
-
-
Reliability
-
Yes
Yes
Yes
Yes
Yes
Yes
Out_Of_Service
-
Yes
Yes
Yes
Yes
Yes
Yes
Units
-
Yes
Yes
Yes
-
-
-
Priority_Array
-
-
Yes
Yes
-
Yes
Yes
Relinquish_Default
-
-
Yes
Yes
-
Yes
Yes
Polarity
-
-
-
-
Yes
Yes
-
Inactive_Text
-
-
-
-
Yes
Yes
Yes
Active_Text
-
-
-
-
Yes
Yes
Yes
*1
For Commandable Object Instances only.
◆
Analog Input Objects
Object
ID
Object Name
(
Network Display
)
Modbus
Address
(Hex.)
Precision
Range
Units
PV
Access
AI1
Analog Input 1 Level
(
Drv Anlog In 1 Level
)
004E
xxxx . x
-
%
R
AI2
Analog Input 2 Level
(
Drv Anlog In 2 Level
)
004F
xxxx . x
-
%
R
AI3
Not Used AI3
(
Not Used AI003
)
-
-
-
-
-
AI4
Not Used AI4
(
Not Used AI004
)
-
-
-
-
-
AI5
Not Used AI5
(
Not Used AI005
)
-
-
-
-
-
AI6
Display Format o1-03
(
Display Format o1-03
)
0502
xxxxx
-
-
R