TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
•
Refer to the drive manual to know if settings
4
and
5
are
available. Settings 4 and 5 are available in A1000
software versions PRG: 1021 and later.
•
The setting range for 1000-Series drives is different for
different software versions. Refer to the Peripheral
Devices & Options section of the drive instruction
manual for more information.
F6-02
(03A3)
Comm External
Fault (EF0)
Detect
Selects the conditions at which
EF0 [Option Card External
Fault]
is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
F6-03
(03A4)
Comm External
Fault (EF0)
Select
Sets the method to stop the motor or let the motor continue
operating when the drive detects an
EF0 [Option Card
External Fault]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When you set this parameter to
3
, the drive will continue
operation after it detects a fault. If you set this parameter
to 3, make sure that you install an emergency stop switch.
1
(0 - 3)
F6-04
(03A5)
bUS Error
Detection Time
Sets the delay time for error detection if a
bUS
error occurs.
Note:
Available for option card software versions VST800265
and later.
2.0 s
(0.0 - 5.0)
F6-07
(03A8)
Multi-Step Ref
@ NetRef/
ComRef
0 : Disable Multi-Step References
1 : Enable Multi-Step References
0
(0, 1)
F6-08
(036A)
Comm Parameter
Reset @Initialize
Selects whether communication-related parameters
F6-xx and
F7-xx
are set back to original default values when you use
parameter
A1-03 [Initialize Parameters]
to initialize the drive.
0 : No Reset - Parameters Retained
1 : Reset - Back to Factory Default
Note:
When you set
F6-08
to
1
and you then use
A1-03
to
initialize the drive, the drive will not change this setting
value.
0
(0, 1)
F6-14
(03BB)
bUS Error Auto
Reset
Sets the drive to automatically reset from a
bUS
error after
reestablishing communications.
0 : Disabled
1 : Enabled
0
(0, 1)