TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
21
A - Drive grounding terminal (FE)
B - Option
C - Included screws
D - Ground screw
E -
Drive front cover
F -
Keypad
G - LED label
H - Ground wire
I -
Option terminal block TB1
J -
Insertion point for connector CN5-
A
K - Connector CN5-A
Figure 5.8 Drive Components with Option
Install the Option
Use this procedure to install the option.
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an
energized drive. Before servicing, disconnect all power to the equipment and wait for the time specified on
the warning label at a minimum. The internal capacitor stays charged after the drive is de-energized. The
charge indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc. When all indicators
are OFF, measure for dangerous voltages to make sure that the drive is safe. If you do work on the drive
when it is energized, it will cause serious injury or death from electrical shock.