Setting 2: External Reference 1/2 Selection
This function switches the Run command and frequency reference source between External reference 1 and 2 if the drive is
in the REMOTE mode.
Status
Description
Open
External reference 1 is used (defined by parameters b1-01 and b1-02)
Closed
External reference 2 is used (defined by parameters b1-15 and b1-16)
Note:
Default drive settings do not allow switching between External reference 1 and 2 during run.
Refer to b1-07: LOCAL/REMOTE Run
if this feature is required by the application.
Setting 3 to 5: Multi-Step Speed Reference 1 to 3
Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs.
Refer to d1: Frequency Reference on page
for details.
Setting 6: Jog Reference Selection
The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.
Frequency Reference on page 182
for details.
Setting 7: Accel/Decel Time Selection 1
Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04).
Refer to C1-01 to C1-04: Accel, Decel
Setting 8, 9: Baseblock Command (N.O., N.C.)
When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb alarm
flashes on the digital operator to indicate baseblock. When baseblock ends while a Run command is active, the drive performs
Speed Search to restart the motor.
Digital Input Function
Drive Operation
Input Open
Input Closed
Setting 8 (N.O.)
Normal operation
Baseblock (Interrupt output)
Setting 9 (N.C.)
Baseblock (Interrupt output)
Normal operation
WARNING! Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake when
the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a slipping load
from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.
Begin Speed Search from the
previous frequency reference
Run command
Baseblock input
Frequency
reference
Output frequency
OFF
ON
Output off, motor coasts
ON
Baseblock
release
Figure 5.38 Baseblock Operation During Run
Setting A: Accel/Decel Ramp Hold
When the digital input programmed for the Accel/decel ramp hold function closes, the drive locks (holds) the output frequency.
Acceleration or deceleration resumes when the input is reopened.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive saves the output frequency to memory when the Ramp
Hold input is closed. When the drive is restarted after stop or after power supply interruption, the saved output frequency
becomes the frequency reference (provided that the Accel/decel ramp hold input is still closed).
Reference Hold Function Selection on page 186
5.7 H: Terminal Functions
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
207
5
Parameter Details