No.
Name
Unit
Default Settings
–
Model CIMR-P
o
–
2A0110
2A0138
2A0169
2A0211
o2-04
Drive Model Selection
Hex.
70
72
73
74
E2-11
Motor Rated Power
kW (HP)
30
(40)
37
(50)
45
(60)
55
(75)
b3-04
V/f Gain during Speed Search
%
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
2.00
b8-04
Energy Saving Coefficient Value
–
46.27
38.16
35.78
31.35
C5-17
Motor Inertia
kgm
2
0.220
0.273
0.333
0.490
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
105
131
160
190
E2-02
Motor Rated Slip
Hz
1.8
1.33
1.6
1.43
E2-03
Motor No-Load Current
A
21.9
38.2
44
45.6
E2-05
Motor Line-to-Line Resistance
Ω
0.064
0.039
0.03
0.022
E2-06
Motor Leakage Inductance
%
20.8
18.8
20.2
20.5
E2-10
Motor Iron Loss for Torque Compensation
W
699
823
852
960
L2-02
Momentary Power Loss Ride-Thru Time
s
2
2
2
2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1.1
1.1
1.2
1.3
L2-04
Momentary Power Loss Voltage Recovery Ramp Time
s
0.6
0.6
1
1
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.323
0.32
0.387
0.317
L8-02
Overheat Alarm Level
°C
130
130
130
125
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
B.16 Defaults by Drive Model