n
Serial Communication Terminals
Table 3.9 Control Circuit Terminals: Serial Communications
Type
No.
Signal Name
Function (Signal Level)
MEMOBUS/Modbus
Communication
R+
Communications input (+)
MEMOBUS/Modbus communication: Use an
RS-422 or RS-485 cable to connect the drive.
RS-422/RS-485
MEMOBUS/Modbus
communication
protocol
115.2 kbps (max.)
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
IG
Shield ground
0 V
u
Terminal Configuration
The control circuit terminals are arranged as shown in
E(G) IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC
24V
RP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
E(G) IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC A1 A2 A3 FM AM AC
24V
RP AC
M1 M2 M3 M4
MD ME MF
MA MB MC
TB5
Figure 3.31 Control Circuit Terminal Arrangement
n
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
. For simpler and more reliable wiring, use crimp ferrules on the wire
for ferrule terminal types and sizes.
Table 3.10 Wire Gauges
Terminal
Screw
Size
Tightening
Torque
N
•
m
(lb. in)
Bare Wire Terminal
Ferrule-Type Terminal
Wire Type
Applicable
wire size
mm
2
(AWG)
Recomm.
wire size
mm
2
(AWG)
Applicable
wire size
mm
2
(AWG)
Recomm.
wire size
mm
2
(AWG)
S1-S8, SC, SN, SP
M3
0.5 to 0.6
(4.4 to 5.3)
Stranded wire:
0.2 to 1.0
(24 to 16)
Solid wire:
0.2 to 1.5
(24 to 16)
0.75 (18)
0.25 to 0.5
(24 to 20)
0.5 (20)
Shielded wire,
etc.
RP, V+, A1, A2, A3,
AC, 24 V
MA, MB, MC, MD, ME,
MF
M1-M4
FM, AM, AC
R+, R-, S+, S-, IG
3.9 Control Circuit Wiring
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
97
3
Electrical Installation