1.2 General Description
u
P1000 Model Selection
for drive selection depending on motor power.
Note:
The models and capacities in shown here are based on standard settings and operation conditions. Higher carrier frequencies and higher
ambient temperatures require derating.
Table 1.1 P1000 Models
Motor Power
HP
Three-Phase 200 V Class
Three-Phase 400 V Class
Three-Phase 600 V Class
Drive Model
Rated Output
Current (A)
Drive Model
Rated Output
Drive Model
Rated Output
0.75
2A0004
3.5
4A0002
2.1
–
–
1
2A0006
6
–
–
–
2
2A0008
8
4A0004
4.1
5A0003
2.7
3
2A0010
9.6
4A0005
5.4
5A0004
3.9
2A0012
12
4A0007
6.9
–
–
5
2A0018
17.5
4A0009
8.8
5A0006
6.1
7.5
2A0021
21
4A0011
11.1
5A0009
9
10
2A0030
30
4A0018
17.5
5A0011
11
15
2A0040
40
4A0023
23
5A0017
17
20
2A0056
56
4A0031
31
5A0022
22
25
2A0069
69
4A0038
38
5A0027
27
30
2A0081
81
4A0044
44
5A0032
32
40
2A0110
110
4A0058
58
5A0041
41
50
2A0138
138
4A0072
72
5A0052
52
60
2A0169
169
4A0088
88
5A0062
62
75
2A0211
211
4A0103
103
5A0077
77
100
2A0250
250
4A0139
139
5A0099
99
125
2A0312
312
4A0165
165
5A0125
125
150
2A0360
360
4A0208
208
5A0145
145
175
2A0415
415
–
–
–
–
200
–
–
4A0250
250
5A0192
192
250
–
–
4A0296
296
5A0242
242
300
–
–
4A0362
362
–
–
350
–
–
4A0414
414
–
–
400-450
–
–
4A0515
515
–
–
500-550
–
–
4A0675
675
–
–
750
–
–
4A0930
930
–
–
1000
–
–
4A1200
1200
–
–
<1> These values assume the carrier frequency is not set higher than 8 kHz.
<2> These values assume the carrier frequency is not set higher than 5 kHz.
<3> These values assume the carrier frequency is set to 2 kHz.
Note:
Current derating is required when setting the carrier frequency higher.
Refer to Drive Derating Data on page 407