E2: Motor 1 Parameters
No.
(Addr.
Hex)
Name
Description
Values
Page
E2-01
(30E)
Motor Rated Current
Sets the motor nameplate full load current in amps. Automatically set during
Auto-Tuning.
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current
E2-02
(30F)
Motor Rated Slip
Sets the motor rated slip. Automatically set during Auto-Tuning.
Min.: 0.00 Hz
Max.: 20.00 Hz
E2-03
(310)
Motor No-Load Current
Sets the no-load current for the motor. Automatically set during Auto-Tuning. Default:
Min.: 0 A
Max.: E2-01
E2-04
(311)
Number of Motor Poles
Sets the number of motor poles. Automatically set during Auto-Tuning.
Default: 4
Min.: 2
Max.: 48
E2-05
(312)
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance. Automatically set during
Auto-Tuning.
Min.: 0.000 Ω
Max.: 65.000 Ω
E2-06
(313)
Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor
rated voltage. Automatically set during Auto-Tuning.
Min.: 0.0%
Max.: 40.0%
E2-10
(317)
Motor Iron Loss for Torque
Compensation
Sets the motor iron loss.
Min.: 0 W
Max.: 65535 W
E2-11
(318)
Motor Rated Power
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set
during Auto-Tuning.
Min.: 0.00 kW
Max.: 650.00 kW