No.
(Addr.
Hex)
Name
Description
Values
Page
S2-17
(3216)
Sequence Timer 4 Stop Time
Sets the stop time for timer 4. The value must be set greater than or equal to
S2-16.
Default: 00:00
Min.: 00:00
Max.: 24:00
S2-18
(3217)
Sequence Timer 4 Day
Selection
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-19
(3218)
Sequence Timer 4 Selection
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
S2-20
(3219)
Sequence Timer 4 Reference
Source
Selects the frequency reference source used for running the drive when
sequence timer 4 is active (only applicable when S2-19 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
Default: 0
Range: 0 to 7
u
S3: Secondary PI (PI2) Control
No.
(Addr.
Hex)
Name
Description
Values
Page
S3-01
(321A)
Secondary PI Enable
Selection
Determines when the secondary PI controller is enabled.
0: Disabled
1: Always
2: Drive running
3: Motor running
Note:
Setting 3 does not run the motor at zero speed, baseblock, or in
DC injection.
Default: 0
Range: 0 to 3
S3-02
(321B)
Secondary PI User Display
Sets the scale value of 100% PI input.
Default: 10000
Min.: 0
Max.: 60000
S3-03
(321C)
Secondary PI Display Digits
Sets the decimal place display for secondary PI units.
0: No decimal places
1: One decimal place
2: Two decimal places
3: Three decimal places
Default: 2
Range: 0 to 3
B.12 S: Special Application
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
475
B
Parameter List