Table B.7 400 V Class Drives Default Settings by Drive Model
No.
Name
Unit
Default Settings
–
Model CIMR-P
o
–
4A0002
4A0004
4A0005
4A0007
o2-04
Drive Model Selection
Hex.
92
93
94
95
E2-11
Motor rated power
kW (HP)
0.75
(0.75)
1.5
(2)
2.2
(3)
3.0
(3)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
447.4
338.8
313.6
265.7
C5-17
Motor Inertia
kgm
2
0.0028
0.0068
0.0088
0.0158
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
1.6
3.1
4.2
5.7
E2-02
Motor Rated Slip
Hz
2.6
2.5
3
2.7
E2-03
Motor No-Load Current
A
0.8
1.4
1.5
1.9
E2-05
Motor Line-to-Line Resistance
Ω
22.459
10.1
6.495
4.360
E2-06
Motor Leakage Inductance
%
14.3
18.3
18.7
19
E2-10
Motor Iron Loss for Torque Compensation
W
26
53
77
105
L2-02
Momentary Power Loss Ride-Thru Time
s
0.1
0.2
0.3
0.5
L2-03
Momentary Power Loss Min. Baseblock Time
s
0.3
0.4
0.5
0.5
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.3
0.3
0.3
0.3
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.142
0.166
0.145
0.145
L8-02
Overheat Alarm Level
°C
110
110
110
110
L8-35
Installation Method Selection
–
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
B.16 Defaults by Drive Model
492
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual