Register No.
Contents
002EH
Reserved
002FH
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H
Reserved
0031H
DC Bus Voltage, 1 Vdc units
0032H to 0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type
0035H
Product Code 2 [ASCII], Region Code
0036H, 0037H
Reserved
0038H
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
PID Input, 0.1% units, signed, 100% / max. output frequency
003AH
PID Output, 0.1% units, signed, 100% / max. output frequency
003BH, 003CH
Reserved
003DH
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
003EH
Output Frequency
r/min
003FH
0.01% units
0040H to 004AH
Used for various monitors U1-
oo
.
Refer to U: Monitors on page 479
for parameter details.
004BH
Drive status (U1-12)
bit 0
During Run
bit 1
During Zero Speed
bit 2
During Reverse Run
bit 3
During Fault Reset Signal Input
bit 4
During Speed Agree
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
During Operation Error (oPE
oo
)
bit 9
During Momentary Power Loss
bit A to B
Reserved
bit E
ComRef status, NetRef status
bit F
ComCtrl status, NetCtrl status
004CH to 007EH
Used for various monitors U1-
oo
, U4-
oo
, U5-
oo
and U6-
oo
.
Refer to U2: Fault Trace on page 481
and
007FH
Alarm Code,
Refer to Alarm Register Contents on page 535
0080H to 0097H
Used for monitors U2-
oo
, U3-
oo
.
Refer to U: Monitors on page 479
for register value descriptions.
0098H
High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
00ACH to 00AFH
Reserved
C.9 MEMOBUS/Modbus Data Table
524
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual