![background image](http://html.mh-extra.com/html/yaskawa/jusp-ns115/jusp-ns115_user-manual_907076035.webp)
3 Wiring
3.3.4 Interface Circuits
3-10
Photocoupler output circuits are used for servo alarm, servo ready, and other sequence
output signal circuits.
Connect a photocoupler output circuit through a relay or line receiver circuit.
Note: The maximum allowable voltage and current capacities for
photocoupler output circuits are as follows:
• Voltage: 30 VDC max.
• Current: 50 mA DC max.
5 to 24 VDC
Relay
5 to 12 VDC
0V
0V
0V
0V
SERVOPACK
end
SERVOPACK
end