6.1 Parameter Limits and Standard Settings with NS115
6-5
6
6.1.2 Standard Settings for CN1 I/O Signals
The standards settings for CN1 I/O signals when the NS115 is mounted are described below.
The parameters can be set as described for standard applications.
Fig. 6.1 Standard CN1 I/O Signal Settings
Table 6.2 Factory Settings and Standard Settings for CN1 I/O Signals
Pn No.
Description
Factory Setting
Standard
Setting
Pn50A
Input signal selections 1
2881
2881
Pn50B
Input signal selections 2
6583
8883
Pn511
Input signal selections 5
8888
6541
Pn50E
Output signal selections 1
3211
3001
Pn50F
Output signal selections 2
0000
0200
Pn510
Output signal selections 3
0000
0000
SGDH SERVOPACK
CN1
Not used
/DEC
P-OT
N-OT
/EXT1
/EXT2
/EXT3
/COIN+
/COIN
/BK+
/BK
/S RDY+
/S RDY
40 (SI0)
41 (SI1)
42 (SI2)
43 (SI3)
44 (SI4)
45 (SI5)
46 (SI6)
25
26
27
28
29
30
(SO1)
(SO2)
(SO3)