2.2 Servopacks
2 -9
2.2.5 Installation
Follow the procedure below to install multiple Servopacks side by side in a control panel.
Cooling fan
50 mm (1.97 in) min.
10 mm (0.39 in) min.
30 mm (1.18 in) min.
Cooling fan
50 mm (1.97 in) min.
J
J
Servopack Orientation
Install the Servopack perpendicular to the wall so the front panel containing connectors faces
outward.
J
J
Cooling
Asshown in the figure above, allowsufficient space around each Servopack for cooling by cool-
ing fans or natural convection.
J
J
Side-by-side Installation
When installing Servopacks side by side as shown in the figure above, allow at least 10 mm
(0.39 in) between and at least 50 mm (1.97 in) above and below each Servopack. Install cooling
fansabove the Servopacksto avoid excessive temperature rise and tomaintain eventemperature
inside the control panel.
J
J
Environmental Conditions in the Control Panel
D
Ambient Temperature:
0 to 55
°
C
D
Humidity:
90% RH or less
D
Vibration:
0.5 G (4.9 m/s
2
)
D
Condensation and Freezing: None
D
Ambient Temperature for Long-term Reliability:
45
°
C max.