5.2 Settings According to Host Controller
5 -41
Reference
voltage
(V)
Reference torque
This reference voltage is set.
Rated torque
Two speed limit functions during torque control are available by the user constant setting as
shown below.
Pn002.1 setting
Description
0
Uses speed limit set by Pn407. (internal speed limit function)
1
Uses V-REF (CN1-5 and 6) as external speed limit input and sets speed
limit by voltage which input to V-REF and Pn300. (external speed limit
function)
Internal speed limit function
Pn407
Speed Limit during
Torque Control
Unit:
r/min
Setting
Range:
0 to 10000
Factory
Setting:
10000
Speed/Torque
Control
The user constant sets a motor speed limit when torque control is selected.
It is used to prevent excessive equipment speed during torque control.
Since the speed limit detection signal /VLT functions the same in torque control asthe /CLT sig-
nal, see 5.1.3
Limiting Torque,
where the /CLT signal is described.
Motor speed
Torque Control Range
Speed limit
Torque
control
range
Torque
The maximum speed of the Servomotor will be used if Pn407 is set to a value higher than the
maximum speed of the Servomotor.
External speed limit function
This is function uses V-REF (CN1-5) as external speed limit input and sets input voltage range
by Pn300. Set the range according to host computer and the output state of external circuit.
Pn300
Speed
Reference Input
Gain
Unit:
0.01V/Rated
Speed
Setting
Range:
150 to 3000
Factory
Setting:
600
Speed/Torque
Control
The factory setting is
±
1% of the rated motor speed or 6 V.