User Constant Settings and Functions
5.2.2 Position Reference
5 -16
Connection Example 2: Open-collector Output
Set limiting resistor R1 so that input current, i, falls within the following range:
CN1-15
CLR
P: Indicates twisted-pair wires.
Vcc
PULS
/PULS
CN1-7
CN1-8
P
CN1-14
Servopack
Photocoupler
150
W
/CLR
SIGN
/SIGN
CN1-11
CN1-12
Host controller
R1
i
Tr1
P
R1
P
R1
Input current i: 7 to 15 mA
D
With a Vcc of +12 V: R1 = 1 k
W
D
When Vcc is +5 V: R1 = 180
W
Note
The following table shows the signal logic for an open-collector output.
When Tr1 is ON
Equivalent to high-level input
When Tr1 is OFF
Equivalent to low-level input
This circuit uses the 12-V power supply built into the Servopack. Input is not insulated.
CN1-11
CLR
SIGN
PULS
CN1-15
CN1-18
Servopack
+12 V
Photocoupler
1 k
W
150
W
CN1-7
CN1-3
CN1-8
/PULS
PL1
Approx.
9 mA
Tr1
ON: 1.5 V max.
CN1-13
CN1-12
/SIGN
PL2
CN1-14
/CLR
PL3
CN1-1
P: Indicates twisted-pair wires.
Host controller
P
P
P
The noise margin of the input signal will decrease if the reference pulse is given using an open-collector output.
Set user constant Pn200.3 to 1 if the position drifts due to noise.
5
A
EXAMPLE
"
IMPORTANT